SiBE37-701_B
Troubleshooting by Remote Controller
Troubleshooting
254
Outdoor Unit
LA
l
Malfunction of power unit
—
LC
l
Malfunction of transmission between inverter and control PCB
P1
l
Inverter over-ripple protection
P4
l
Malfunction of inverter radiation fin temperature rise sensor
PJ
l
Faulty field setting after replacing main PCB or faulty combination of PCB
System
U0
k
Refrigerant shortage alert
U1
l
Reverse phase, open phase
U2
l
Power supply insufficient or instantaneous failure
U3
l
Check operation is not executed
U3
k
Check operation is not completed.
U4
l
Malfunction of transmission between indoor units and outdoor units
U5
l
Malfunction of transmission between indoor units
U5
h
Malfunction of transmission between remote controller and indoor unit
U7
l
Transmission failure (Across outdoor units)
U8
l
Malfunction of transmission between main and sub remote controllers
U9
l
Malfunction of transmission between indoor and outdoor units in the same
system
UA
l
Improper combination of indoor and outdoor units, indoor units and remote
controller
UC
k
Address duplication of centralized controller
UE
l
Malfunction of transmission between centralized controller and indoor unit
UF
l
System is not set yet
UH
l
Malfunction of system, refrigerant system address undefined
Centralized
Remote
Controller
and
Schedule
Timer
M1
k
or
h
PCB defect
M8
k
or
h
Malfunction of transmission between optional controllers for centralized
control
MA
k
or
h
Improper combination of optional controllers for centralized control
MC
k
or
h
Address duplication, improper setting
Heat
Reclaim
Ventilation
64
k
Indoor unit’s air thermistor error
—
65
k
Outside air thermistor error
—
6A
k
Damper system alarm
—
6A
l
Damper thermistor error
—
6F
k
Malfunction of simple remote controller
—
6H
k
Malfunction of door switch or connector
—
94
l
Internal transmission error
—
k
: ON
h
: OFF
l
: Blink
Malfunction
code
Operation
lamp
Malfunction contents
Page
Referred
The system operates for malfunction codes indicated in black squares, however, be sure to check and repair.
Summary of Contents for REYQ8-48PY1B
Page 1: ...Service Manual REYQ8 48PY1B R 410A Heat Recovery 50Hz SiBE37 701_B ...
Page 456: ...Piping Installation Point SiBE37 701_B 445 Appendix ...
Page 460: ...Example of connection SiBE37 701_B 449 Appendix ...
Page 476: ...Revision History Date News No Contents 2010 9 10 M 10011 Correction of service manual ...