Troubleshooting by Indication on the Remote Controller
SiBE37-701_B
357
Troubleshooting
3.55
“
U9
”
Indoor Unit: Malfunction of Transmission between
Indoor and Outdoor Units in the Same System
Remote
Controller
Display
U9
Applicable
Models
All indoor unit models
REYQ8P~48P
Method of
Malfunction
Detection
Detect malfunction signal for the other indoor units within the circuit by outdoor unit PCB.
Malfunction
Decision
Conditions
When the malfunction decision is made on any other indoor unit within the system concerned.
Supposed
Causes
Malfunction of transmission within or outside of other system
Malfunction of electronic expansion valve in indoor unit of other system
Defect of PCB of indoor unit in other system
Improper connection of transmission wiring between indoor and outdoor unit
Troubleshooting
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Continue operation.
YES
Turn on all indoor units.
NO
NO
YES
All the units are
indicating “
U9
”.
"
U9
" has been
displayed for 2
minutes or more.
Re-diagnose by display after
passage of 2 minutes or more.
The outdoor unit PCB indicated by
the malfunction code
U9
is normal.
Check for the indoor unit of other
system, and then conduct
troubleshooting by diagnosis
according to the Malfunction Code
Flowchart.
Summary of Contents for REYQ8-48PY1B
Page 1: ...Service Manual REYQ8 48PY1B R 410A Heat Recovery 50Hz SiBE37 701_B ...
Page 456: ...Piping Installation Point SiBE37 701_B 445 Appendix ...
Page 460: ...Example of connection SiBE37 701_B 449 Appendix ...
Page 476: ...Revision History Date News No Contents 2010 9 10 M 10011 Correction of service manual ...