SiBE37-701_B
Refrigerant Flow for Each Operation Mode
Refrigerant Circuit
100
Operation of refrigerant regulator
1. Recovery of refrigerant
Surplus refrigerant is recovered to refrigerant regulator by opening of SVL and SVG when
the indoor unit load is small.
2. Discharge of refrigerant
Discharge refrigerant from refrigerant regulator by opening of SVC when the load of the
outdoor unit is large.
3. Pressure regulating valve (Refrigerant regulator)
The circuit will be closed when SVL, SVO, SVG are all closed. In this case, the increased
pressure in the refrigerant regulator will be transferred to the liquid refrigerant pipe side, to
regulate the pressure.
Liquid
Pipe
Tsc
TL
S1NPH
Equalizing
Pipe
SVP
EVT
Tsh
SVE
Tg
20SA
Ta
Tf
Tb
EVM
Right
Pressure
regulating valve
Refrigerant
Regulator
S1PH
Tdi
INV
Suction Pipe
TS_A
S2NPL
SVL
SVO
SVG
Liquid
Pipe
Tsc
TL
S1NPH
Equalizing
Pipe
SVP
EVT
Tsh
SVE
Tg
20SA
Ta
Tf
Tb
EVM
Right
Pressure
regulating valve
Refrigerant
Regulator
S1PH
Tdi
INV
Suction Pipe
TS_A
S2NPL
SVL
SVO
SVG
Summary of Contents for REYQ8-48PY1B
Page 1: ...Service Manual REYQ8 48PY1B R 410A Heat Recovery 50Hz SiBE37 701_B ...
Page 456: ...Piping Installation Point SiBE37 701_B 445 Appendix ...
Page 460: ...Example of connection SiBE37 701_B 449 Appendix ...
Page 476: ...Revision History Date News No Contents 2010 9 10 M 10011 Correction of service manual ...