![Daikin REYQ8-48PY1B Service Manual Download Page 442](http://html.mh-extra.com/html/daikin/reyq8-48py1b/reyq8-48py1b_service-manual_502202442.webp)
List of Electrical and Functional Parts
SiBE37-701_B
431
Appendix
3. List of Electrical and Functional Parts
3.1
Outdoor Unit
3.1.1 REYQ8PY1~12PY1
Item
Name
Symbol
Model
REYQ8PY1
REYQ10PY1
REYQ12PY1
Compressor
Inverter
Type
M1C
JT1GCVDKYR@SA
OC protection
device
14.7A
STD 1
Type
M2C
JT170G-KYE@T
OC protection
device
15.0A
STD 2
Type
M3C
—
OC protection
device
Fan motor
OC protection
device
M1F
3.0A
3.0A
(for General
overseas : 1.14A)
Electronic expansion valve (Main)
Y1E
Fully closed: 0pls Fully open: 1375pls
Electronic expansion valve (Subcooling)
Y2E
Fully closed: 0pls Fully open: 480pls
Electronic expansion valve (Refrigerant charge)
EV
0~480pls
Pressure
protection
High pressure
switch
For M1C
S1PH
OFF: 4.0
MPa ON: 3.0±0.15MPa
For M2C
S2PH
OFF: 4.0
MPa ON: 3.0±0.15MPa
For M3C
S3PH
—
Low pressure sensor
S2NPL
OFF: 0.07MPa
Temperature
protection
Discharge gas temperature
protection
(Discharge pipe thermistor)
R3T
OFF: 135°C
Inverter fin temperature
protection
(Radiator fin thermistor)
R1T
OFF: 93°C
Others
Fuse
For main PCB
F1U
250V AC 10A Class B Time-lag 3.15A AC 250V
F2U
250V AC 10A Class B Time-lag 3.15A AC 250V
For Noise filter
PCB
F1U
250V AC 5A Class B
+
0
−
0.12
+
0
−
0.12
Summary of Contents for REYQ8-48PY1B
Page 1: ...Service Manual REYQ8 48PY1B R 410A Heat Recovery 50Hz SiBE37 701_B ...
Page 456: ...Piping Installation Point SiBE37 701_B 445 Appendix ...
Page 460: ...Example of connection SiBE37 701_B 449 Appendix ...
Page 476: ...Revision History Date News No Contents 2010 9 10 M 10011 Correction of service manual ...