Precautions for New Refrigerant (R-410A)
SiBE37-701_B
461
Precautions for New Refrigerant (R-410A)
2. Torque wrench
Specifications
• Dimension B
Unit:mm
No change in tightening torque
No change in pipes of other sizes
Differences
• Change of dimension B
Only 1/2", 5/8" are extended
3. Vacuum pump with check valve
Specifications
• Discharge speed
z
Maximum degree of vacuum
50 l/min (50Hz)
Select a vacuum pump which is able to keep
60 l/min (60Hz)
the vacuum degree of the system in excess of
• Suction port UNF7/16-20(1/4 Flare)
–100.7 kPa (5 torr – 755 mmHg).
UNF1/2-20 (5/16 Flare) with adaptor
Differences
• Equipped with function to prevent reverse oil flow
• Previous vacuum pump can be used by installing adaptor.
Nominal size
Class-1
Class-2
Previous
1/2
24
26
24
5/8
27
29
27
For class-1: R-407C
For class-2: R-410A
Dimension B
Vacuum pump adaptor
Reverse flow preventive
vacuum adaptor