Troubleshooting by Indication on the Remote Controller
SiBE37-701_B
279
Troubleshooting
Troubleshooting
∗
1. Pull out and insert the connecter once and check it is absolutely connected.
∗
2. Method to check transmission part of indoor PCB.
Turn off the power and remove the connecter X70A of indoor PCB (A1P).
Short-circuit X70A.
After turning on the power, check below numbers under local setting remote control.
(Confirmation: First code NO. at the condition of second code No. 21 on mode No. 41)
↓
★
After confirmation, turn off the power, take off the short-circuit and connect X70A back to
original condition.
Determination
01: Normal
Other than 01: Transmission defect on indoor PCB
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
NO
YES
Connect the connector accurately.
NO
YES
Replace PCB for fan (A2P).
Connect it and operate (It is
possible to have a cause, such
as instantaneous blackout)
Under above local
installation mode, installation
position is
"
01
"
.
Connect the connecter
X70A and turn on the power
again.
Confirm the condition of
transmission on indoor PCB
using local installation mode.
(*2)
Is the connector between indoor PCB
(A1P) and PCB for fan (A2P) accurately
connected? (*1)
NO
YES
"
C1
"
Malfunction
breaks out again.
Replace indoor PCB (A1P).
Summary of Contents for REYQ8-48PY1B
Page 1: ...Service Manual REYQ8 48PY1B R 410A Heat Recovery 50Hz SiBE37 701_B ...
Page 456: ...Piping Installation Point SiBE37 701_B 445 Appendix ...
Page 460: ...Example of connection SiBE37 701_B 449 Appendix ...
Page 476: ...Revision History Date News No Contents 2010 9 10 M 10011 Correction of service manual ...