SiBE37-701_B
Special Control
Function
120
3.1.2 Startup Control in Heating Operation
Actuator
Symbol
Elect.
symbol
Control
before
startup
Startup control
REYQ
REMQ
STEP 1
STEP 2
Compressor 1
—
M1C
M1C
0 Hz
52 Hz+OFF+OFF
52Hz+OFF+OFF+2 STEP / 20
sec.
(Until it reaches
Pc-Pe>0.39 MPa)
Compressor 2
M2C
M2C
Compressor 3
—
M3C
Outdoor unit fan 1
—
M1F
M1F
STEP 4
20SA=ON: STEP 7
20SA=OFF
+1step/15 sec. (When
Pc_max>2.16 MPa)
-1step/15 sec. (When
Pc_max<1.77 MPa)
20SA=ON: STEP 7
20SA=OFF
+1step/15 sec. (When
Pc_max>2.16 MPa)
-1step/15 sec. (When
Pc_max<1.77 MPa)
Outdoor unit fan 2
M2F
M2F
Electronic expansion
valve (Main)
EVM
Y1E
Y3E
Y1E
0 pls
20SA=ON: SH Control
20SA=OFF: 1375 pls
20SA=ON: SH Control
20SA=OFF: 1375 pls
Electronic expansion
valve (Subcooling)
EVT
Y2E
Y5E
Y3E
0 pls
0 pls
0 pls
Electronic expansion
valve (Refrigerant
charge)
EVJ
Y4E
Y2E
80 pls
80 pls
80 pls
Four way valve (Heat
exchanger switch)
20SA
Y2S
Y9S
Y3S
When
outdoor
heat
exchanger
is
evaporator:
ON
When
outdoor
heat
exchanger
is
condenser:
OFF
When outdoor heat
exchanger is evaporator: ON
When outdoor heat
exchanger is condenser:
OFF
When outdoor heat
exchanger is evaporator: ON
When outdoor heat
exchanger is condenser:
OFF
Four way valve (Dual
pressure gas pipe switch)
20SB
Y8S
Y2S
OFF
OFF
OFF
Solenoid valve (Main
bypass)
SVE
Y5S
Y10S
Y6S
OFF
OFF
OFF
Solenoid valve (Hot gas)
SVP
Y4S
Y5S
OFF
OFF
OFF
Solenoid valve
(Refrigerant regulator
liquid pipe)
SVL
Y3S
Y4S
OFF
OFF
OFF
Solenoid valve
(Refrigerant regulator gas
vent pipe)
SVG
Y1S
Y1S
OFF
OFF
OFF
Solenoid valve
(Refrigerant regulator
discharge pipe)
SVO
Y7S
Y7S
OFF
OFF
OFF
Solenoid valve
(Refrigerant regulator
discharge pipe)
SVT
Y6S
Y8S
OFF
OFF
OFF
Ending conditions
A lapse of
60 sec.
A lapse of 15 sec.
•
A lapse of 90 sec.
•
Pc - Pe>0.39 MPa
OR
Summary of Contents for REYQ8-48PY1B
Page 1: ...Service Manual REYQ8 48PY1B R 410A Heat Recovery 50Hz SiBE37 701_B ...
Page 456: ...Piping Installation Point SiBE37 701_B 445 Appendix ...
Page 460: ...Example of connection SiBE37 701_B 449 Appendix ...
Page 476: ...Revision History Date News No Contents 2010 9 10 M 10011 Correction of service manual ...