![Daikin REYQ8-48PY1B Service Manual Download Page 266](http://html.mh-extra.com/html/daikin/reyq8-48py1b/reyq8-48py1b_service-manual_502202266.webp)
Troubleshooting by Remote Controller
SiBE37-701_B
255
Troubleshooting
Malfunction code indication by outdoor unit
PCB
<Monitor mode>
To enter the monitor mode, push the
MODE (BS1) button when in “Setting
mode 1”.
<Selection of setting item>
* Refer to Page 220 for Monitor mode.
* Refer to Page 220 for Monitor mode.
Push the SET (BS2) button and set
the LED display to a setting item.
<Confirmation of malfunction 1>
Push the RETURN (BS3) button once
to display "First digit" of malfunction
code.
<Confirmation of malfunction 2>
Push the SET (BS2) button once to
display "Second digit" of malfunction
code.
<Confirmation of malfunction 3>
Push the SET (BS2) button once to
display "malfunction location".
<Confirmation of malfunction 4>
Push the SET (BS2) button once to
display "master or slave 1 or slave 2"
and "malfunction location".
Detail
description
on next
page.
Push the RETURN (BS3) button and
switches to the initial status of
“Monitor mode”.
* Push the MODE (BS1) button and
returns to “Setting mode 1”.
Malfunctions
Malfunction
code
Description of malfunction
Description of malfunction (PGF)
Remote
controller
PCB malfunction
PCB malfunction
E1
Faulty PCB
Abnormal discharge pressure
HPS activated
E3
Abnormal suction pressure
Pe malfunction
E4
Compressor lock
INV compressor lock detected
E5
OC activation
STD1 compressor lock detected
E6
STD2 compressor lock detected
Overload, overcurrent and abnormal
lock of outdoor unit fan motor
Instantaneous overcurrent of 1DC fan motor
E7
1DC fan motor lock detected
Fan 1 IPM faulty protection detected
Instantaneous overcurrent of 2DC fan motor
2DC fan motor lock detected
Fan 2 IPM faulty protection detected
Electronic expansion valve
malfunction
EVM (main)
E9
EVJ (refrigerant charging)
EVT (subcool heat exchanger)
Positioning signal malfunction of
outdoor unit fan motor
1DC fan motor positioning signal
malfunction
H7
2DC fan motor positioning signal
malfunction
Abnormal outdoor temperature
Ta sensor malfunction (short-circuited
or open)
H9
Abnormal discharge pipe temperature
Td malfunction
F3
Abnormal heat exchanger temperature Refrigerant overcharged
F6
BS unit electronic expansion valve
malfunction
BS EVH disconnected (Y4E)
F9
BS EVL disconnected (Y5E)
BS EVHS disconnected (Y2E)
BS EVLS disconnected (Y3E)
BS EVSC disconnected (Y1E)
Current sensor malfunction
CT1 sensor malfunction (STD
compressor 1)
J2
CT2 sensor malfunction (STD
compressor 2)
CT sensor malfunction (system)
Discharge pipe temperature sensor
malfunction
Tdi sensor malfunction (R31T)
J3
Tds1 sensor malfunction (short-
circuited) (R32T)
Tds2 sensor malfunction (short-
circuited) (R33T)
Heat exchanger gas temperature
sensor malfunction
Tg sensor malfunction (R2T, R11T)
J4
Suction pipe temperature sensor
malfunction
TsA sensor malfunction (short-
circuited) (R8T, R10T)
J5
Heat exchanger temperature sensor
malfunction
Tb sensor malfunction (R4T, R12T)
J6
Liquid pipe temperature sensor
malfunction
Tsc sensor malfunction (R6T, R14T)
J7
TL sensor malfunction (R9T)
Heat exchanger liquid pipe
temperature sensor malfunction
Tf sensor malfunction (R7T, R15T)
J8
Subcool heat exchanger temperature
sensor malfunction
Tsh sensor malfunction (R5T, R13T)
J9
Discharge pressure sensor malfunction Pc sensor malfunction (S1NPH)
JA
Suction pressure sensor malfunction
Pe sensor malfunction (S1NPL)
JC
INV PCB malfunction
Faulty IPM
Current sensor failure confirmation 1
Current sensor failure confirmation 2
IGBT malfunction
L1
Rise in INV radiation fin temperature
Overheat of INV radiation fin temperature
L4
DC output overcurrent
Instantaneous overcurrent of INV
L5
IGBT malfunction
Electronic thermal
Electronic thermal 1
L8
Electronic thermal 2
Loss of synchronization
Speed degradation after startup
Thunder detected
Stall prevention (time limit)
Stall prevention (increased current)
L9
Stall prevention (startup failure)
Abnormal starting waveform
Loss of synchronization
INV transmission malfunction
INV transmission data malfunction
LC
INV transmission malfunction
k
: ON
l
: Blink
h
: OFF
Summary of Contents for REYQ8-48PY1B
Page 1: ...Service Manual REYQ8 48PY1B R 410A Heat Recovery 50Hz SiBE37 701_B ...
Page 456: ...Piping Installation Point SiBE37 701_B 445 Appendix ...
Page 460: ...Example of connection SiBE37 701_B 449 Appendix ...
Page 476: ...Revision History Date News No Contents 2010 9 10 M 10011 Correction of service manual ...