Troubleshooting (OP: Centralized Remote Controller)
SiBE37-701_B
373
Troubleshooting
4.3
“
MA
”
Improper Combination of Optional Controllers for
Centralized Control
Remote
Controller
Display
MA
Applicable
Models
Centralized remote controller intelligent touch controller
Schedule timer
Method of
Malfunction
Detection
Detect the malfunction according to DIII-NET transmission data.
Malfunction
Decision
Conditions
When the schedule timer is set to individual use mode, other central component is present.
When multiple master controller are present.
When the remote control adaptor is present.
Supposed
Causes
Improper combination of optional controllers for centralized control
More than one master controller is connected
Defect of PCB of optional controller for centralized control