6 - PARAMETER DESCRIPTION
See Also
Stop Mode parameter (CFN15) on page 85.
Decel End Level parameter (CFN17) on page 87.
Decel Time parameter (CFN18) on page 87.
Controlled Fault Stop Enable parameter (PFN25) on page 103.
Rated Power Factor parameter (FUN06) on page 127.
Theory of Operation section 7.4, Deceleration Control on page 157.
Decel End Level
CFN 17
LCD Display
Range
1 – 99 % of phase angle firing
(Default 20%)
Description
Stop Mode (CFN15) set to Voltage Deceleration:
The voltage deceleration profile utilizes an open loop S-curve voltage ramp profile. The Decel End Level
parameter sets the ending voltage level for the voltage deceleration ramp profile. The deceleration ending
level is not a precise percentage of actual line voltage, but defines an ending point on the S-curve deceleration
profile.
A typical voltage decel end level setting is between 10% and 20%. If the motor stops rotating before the
deceleration time has expired, increase this parameter value. If the motor is still rotating when the
deceleration time has expired, decrease this parameter value. If the value is set too low a “No Current at Run”
fault may occur during deceleration.
z
NOTE:
The deceleration end level cannot be set greater than the decel begin level.
Stop Mode (CFN15) set to TruTorque Deceleration:
The decel end level parameter sets the ending torque level for the TruTorque deceleration ramp profile.
A typical TruTorque decel end level setting is between 10% and 20%. If the motor stops rotating before the
deceleration time has expired, increase this parameter value. If the motor is still rotating when the
deceleration time has expired, decrease this parameter value.
See Also
Stop Mode parameter (CFN15) on page 85.
Decel Begin Level parameter (CFN16) on page 86.
Decel Time parameter (CFN18) on page 87.
Controlled Fault Stop Enable parameter (PFN25) on page 103.
Theory of Operation section 7.4, Deceleration Control on page 157.
Decel Time
CFN 18
LCD Display
Range
1 – 180 seconds
(Default 15)
CFN: Decel End
17
20 %
CFN: Decel Time
18
15 sec
Summary of Contents for RediStart MX3 Series
Page 9: ...1 Introduction 1...
Page 15: ...2 Technical Specifications 7...
Page 35: ...3 Installation 27...
Page 61: ...4 Keypad Operation 53...
Page 71: ...5 Parameter Groups 63...
Page 79: ...6 Parameter Description 71...
Page 145: ...7 Theory of Operation 137...
Page 188: ...NOTES 180 7 THEORY OF OPERATION...
Page 189: ...8 Troubleshooting Maintenance 181...
Page 208: ...NOTES 200 8 TROUBLESHOOTING MAINTENANCE...
Page 209: ...Appendices 201...
Page 237: ...Publication History Revision Date ECO 00 12 15 06 Initial Release...