Current Transformers
3.7
Current Transformers
3.7.1
CT Mounting
For starters larger than 124 amps, the CTs are shipped loose from the power stack and need to be mounted on the power wiring. Thread
the motor or incoming lead through the CT with the polarity mark towards the line side. (The polarity marks may be a white or yellow
dot, an “X” on the side of the CT, or the white wire.) Each phase has its own CT. The CT must then be attached to the power wiring, at
least three inches from the power wire lugs, using two tie-wraps.
3.7.2
CT Polarity
The CT has a polarity that must be correct for the starter to correctly measure Watts, kW Hours, Power Factor, and for the Power and
TruTorque motor control functions to operate properly.
Each CT has a dot on one side of the flat surfaces. This dot, normally white in color, must be facing in the direction of the line.
CT1 must be on Line L1, CT2 must be on Line L2, CT3 must be on Line L3.
38
3 - INSTALLATION
FRONT VIEW
SIDE VIEW DETAIL
MUST BE A 3" (MIN.)
SPACE BETWEEN CT
AND TOP OF LUG
CUSTOMER MUST FASTEN CT
TO POWER WIRE WITH TWO 1/4"
NYLON WRAPS TO PREVENT
MOVEMENT DURING RUNNING
Dot, or X,
White Wire
Figure 12: Typical CT Mounting
Socket size across flats
Tightening torque
inches
(mm)
Pound-inches
(N-m)
1/8
(3.2)
45
(5.1)
5/32
(4.0)
100
(11.3)
3/16
(4.8)
120
(13.6)
7/32
(5.6)
150
(16.9)
1/4
(6.4)
200
(22.6)
5/16
(7.9)
275
(31.1)
3/8
(9.5)
275
(42.4)
1/2
(12.7)
500
(56.5)
9/16
(14.3)
600
(67.8)
z
NOTE
– For screws with multiple tightening means, the largest torque value associated with the conductor size
shall be marked. Slot length shall be measured at the bottom of the slot.
Table 17: Tightening Torque for Inside Hex Screws
Summary of Contents for RediStart MX3 Series
Page 9: ...1 Introduction 1...
Page 15: ...2 Technical Specifications 7...
Page 35: ...3 Installation 27...
Page 61: ...4 Keypad Operation 53...
Page 71: ...5 Parameter Groups 63...
Page 79: ...6 Parameter Description 71...
Page 145: ...7 Theory of Operation 137...
Page 188: ...NOTES 180 7 THEORY OF OPERATION...
Page 189: ...8 Troubleshooting Maintenance 181...
Page 208: ...NOTES 200 8 TROUBLESHOOTING MAINTENANCE...
Page 209: ...Appendices 201...
Page 237: ...Publication History Revision Date ECO 00 12 15 06 Initial Release...