Analog Input Span
I/O 19
LCD Display
Range
1 – 100%
(Default 100%)
Description
The analog input can be scaled using the Analog Input Span parameter.
Examples:
For a 0-10V input or 0-20mA input, a 100% Analog Input Span setting results in a 0% input reading with a
0V input and a 100% input reading with a 10V input.
For a 0-5V input, a 50% Analog Input Span setting results in a 0% input reading with a 0V input and a 100%
input reading with a 5V input.
For a 4-20mA input, a 80% Analog Input Span setting and a 20% Analog Input Offset setting results in a 0%
input reading at 4mA and a 100% input reading at 20mA.
z
NOTE:
Input signal readings are clamped at a 100% maximum.
Example: 4ma = 0% input, 20ma = 100% input
See Also
Analog Input Trip Level parameter (I/O17) on page 114.
Analog Input Trip Time parameter (I/O18) on page 114.
Analog Input Offset parameter (I/O20) on page 116.
Starter Type parameter (FUN07) on page 128.
Theory of Operation section 7.11, Phase Control on page 173.
Theory of Operation section 7.12, Current Follower on page 175.
115
6 - PARAMETER DESCRIPTION
I/O:
Ain Span
19
100 %
Analog Input
Reading %
100%
Ain Span = 80%
2V / 4mA
0%
20% Ain
Offset
10V / 20mA
Input Signal
Summary of Contents for RediStart MX3 Series
Page 9: ...1 Introduction 1...
Page 15: ...2 Technical Specifications 7...
Page 35: ...3 Installation 27...
Page 61: ...4 Keypad Operation 53...
Page 71: ...5 Parameter Groups 63...
Page 79: ...6 Parameter Description 71...
Page 145: ...7 Theory of Operation 137...
Page 188: ...NOTES 180 7 THEORY OF OPERATION...
Page 189: ...8 Troubleshooting Maintenance 181...
Page 208: ...NOTES 200 8 TROUBLESHOOTING MAINTENANCE...
Page 209: ...Appendices 201...
Page 237: ...Publication History Revision Date ECO 00 12 15 06 Initial Release...