Altitude Derating
Benshaw's starters are capable of operating at altitudes up to 3,300 feet (1000 meters) without requiring altitude derating. Table 12
provides the derating percentage to be considered when using a starter above 3,300 feet (1000 meters).
Real Time Clock
2.7
Real Time Clock
The MX
3
comes with a real time clock. The user can enter the actual time and the starter will use this time when it logs faults in the fault
recorder as well as events in the event recorder. This can help with troubleshooting. The system clock does not recognize daylight
savings time.
Accuracy: +- 1 minute per month
Range: 1/1/1972 to 1/1/2107 with automatic leap year compensation.
Approvals
2.8
Approvals
MX
3
Control Card set is UL, cUL Recognized
Certificate of Compliance
2.9
Certificate of Compliance
CE Mark, See Appendix E on page 208.
26
2 - TECHNICAL SPECIFICATIONS
Altitude
Percent Derating (Amps)
3300 Feet
1006 meters
0.0%
4300 Feet
1311 meters
3.0%
5300 Feet
1615 meters
6.0%
6300 Feet
1920 meters
9.0%
7300 Feet
2225 meters
12.0%
8300 Feet
2530 meters
15.0%
9300 Feet
2835 meters
18.0%
Table 12: Altitude Derating
Summary of Contents for RediStart MX3 Series
Page 9: ...1 Introduction 1...
Page 15: ...2 Technical Specifications 7...
Page 35: ...3 Installation 27...
Page 61: ...4 Keypad Operation 53...
Page 71: ...5 Parameter Groups 63...
Page 79: ...6 Parameter Description 71...
Page 145: ...7 Theory of Operation 137...
Page 188: ...NOTES 180 7 THEORY OF OPERATION...
Page 189: ...8 Troubleshooting Maintenance 181...
Page 208: ...NOTES 200 8 TROUBLESHOOTING MAINTENANCE...
Page 209: ...Appendices 201...
Page 237: ...Publication History Revision Date ECO 00 12 15 06 Initial Release...