96
6 - PARAMETER DESCRIPTION
Residual Ground Fault Trip Level
PFN 07
LCD Display
Range
Off, 5 – 100 % FLA
(Default Off)
Description
The Residual Ground Fault Trip Level parameter sets a ground fault current trip or indicate level that can be
used to protect the system from a ground fault condition. The starter monitors the instantaneous sum of the
three line currents to detect the ground fault current.
Ground Fault Trip: The MX
3
will trip with a ground fault indication if:
- No other fault currently exists.
- Ground fault current is equal to or greater than the GF Trip Level for a time
period greater than the GF Trip Delay (PFN09).
Once the starter recognizes a ground fault condition, it shuts down the motor and declares a Fault 38 (Ground
Fault).
If a programmable relay (I/O 10-15) is set to "GROUND FAULT", the starter energizes the relay when the
condition exists.
A typical value for the ground fault current setting is 10% to 20% of the full load amps of the motor.
z
NOTE:
This type of protection is meant to provide machine ground fault protection only. It is not meant to
provide human ground fault protection.
z
NOTE:
The MX
3
residual ground fault protection function is meant to detect ground faults on solidly
grounded systems. Use on a high impedance or floating ground power system may impair the usefulness of
the MX
3
residual ground fault detection feature.
z
NOTE:
Due to uneven CT saturation effects and motor and power system variations, there may be small
values of residual ground fault currents measured by the MX
3
during normal operation.
See Also
Ground Fault Trip Time (PFN09) on page 98.
Auto Reset parameter (PFN23) on page 102.
Controlled Fault Stop Enable parameter (PFN25) on page 103.
Relay Output Configuration parameters (I/O 10 - 15) on page 112.
PFN: Resid GF Lvl
07
Off
Alarm
Condition
Fault
Trip
% FLA
Ground Fault
Trip Time
PFN 09
Residual Gnd Fault
Level
PFN 07
Time
Summary of Contents for RediStart MX3 Series
Page 9: ...1 Introduction 1...
Page 15: ...2 Technical Specifications 7...
Page 35: ...3 Installation 27...
Page 61: ...4 Keypad Operation 53...
Page 71: ...5 Parameter Groups 63...
Page 79: ...6 Parameter Description 71...
Page 145: ...7 Theory of Operation 137...
Page 188: ...NOTES 180 7 THEORY OF OPERATION...
Page 189: ...8 Troubleshooting Maintenance 181...
Page 208: ...NOTES 200 8 TROUBLESHOOTING MAINTENANCE...
Page 209: ...Appendices 201...
Page 237: ...Publication History Revision Date ECO 00 12 15 06 Initial Release...