APPENDIX F - MODBUS REGISTER MAP
Absolute Register Address
Description
Range
Units
30176/40176
Analog Input Trip Type
0:
Low – Fault below preset level
1:
High – Fault above preset level
–
30177/40177
Analog Input Trip Level
0 – 100
%
30178/40178
Analog Input Trip Delay Time
1 – 900
100 mSec
30179/40179
Analog Input Span
1 – 100
%
30180/40180
Analog Input Offset
0 – 99
%
30181/40181
Analog Output Function
0:
Off (no output)
1:
0 – 200% Current
2:
0 – 800% Current
3:
0 – 150% Voltage
4:
0 – 150% Overload
5:
0 – 10kW
6:
0 – 100kW
7:
0 – 1MW
8:
0 – 10MW
9:
1 – 100% Analog Input
10: 0 – 100% Firing
11: Calibration (full output)
–
30182/40182
Analog Output Span
1 – 125
%
30183/40183
Analog Output Offset
0 – 99
%
30184/40184
Inline Enable
0:
Disabled
1:
Enabled
–
30185/40185
Inline Delay Time
10 – 100
100 mSec
30186/40186
Bypass Feedback Time
1 – 50
100 mSec
30187/40187
Keypad Stop
0:
Disabled
1:
Enabled
–
30188/40188
Modbus Timeout Enable
0:
Disabled
1:
Enabled
–
30189/40189
Modbus Timeout
1 – 120
Sec
30190/40190
CT Ratio (x:1)
0:
72:1
1:
96:1
2:
144:1
3:
288:1
4:
864:1
5:
2640:1
6:
3900:1
7
5760:1
8:
8000:1
9:
14400:1
10: 28800:1
11: 50:5
12: 150:5
13: 250:5
14: 800:5
15: 2000:5
16: 5000:5
–
30191/40191
Auto Start
0:
Disabled
1:
Start after power applied
2:
Start after fault reset
3:
Starter after power applied and after
fault reset
–
30192/40192
Energy Saver Enable
0:
Disabled
1:
Enabled
–
30193/40193
Heater / Anti-Windmill Enable
0:
Disabled
1:
Enabled
–
30194/40194
Heater / Anti-Windmill Level
1 – 40
% FLA
30195/40195
Starter Type
0:
Normal (Outside Delta)
1:
Inside Delta
2:
Wye-Delta
3:
Phase Controller
4:
Current Follower
5:
Across the Line (Full Voltage)
–
Summary of Contents for RediStart MX3 Series
Page 9: ...1 Introduction 1...
Page 15: ...2 Technical Specifications 7...
Page 35: ...3 Installation 27...
Page 61: ...4 Keypad Operation 53...
Page 71: ...5 Parameter Groups 63...
Page 79: ...6 Parameter Description 71...
Page 145: ...7 Theory of Operation 137...
Page 188: ...NOTES 180 7 THEORY OF OPERATION...
Page 189: ...8 Troubleshooting Maintenance 181...
Page 208: ...NOTES 200 8 TROUBLESHOOTING MAINTENANCE...
Page 209: ...Appendices 201...
Page 237: ...Publication History Revision Date ECO 00 12 15 06 Initial Release...