The short lockout is displayed when the RTD module senses a shorted RTD.
z
NOTE:
XX:XX is the time remaining until the lockout releases.
4.4.9
Alarm Screen
When an alarm is present, the word “Alarm” is displayed on the operate screen. Pressing the [ENTER] key displays more information
about the alarm.
Procedure for Setting Data
4.5
Procedure for Setting Data
Select a parameter that is to be changed. To change Motor FLA from 10 Amps to 30 Amps:
From the main screen:
Press [MENU] key and the display shows QST: (Quick Start) screen.
Press [UP] key once to Motor FLA (QST 01).
Press [ENTER] key once, the cursor starts to flash in the one’s place.
Press [LEFT] key once, the cursor flashes in the ten’s place.
Press [UP] arrow to increase the value, for a value of 30, press twice.
Press [ENTER] to store the value.
Press [UP] arrow to change another parameter in QST.
Press [MENU] to change another parameter in another group.
Press [LEFT] arrow to go back to the main screen.
61
4 - KEYPAD OPERATION
Alarm ##
Alarm Name
T Ready Ia= 0.0A
Stopped Va= 480V
QST: Jump Code
00 1
QST: Motor FLA
01 10 Amp
QST: Motor FLA
01 1
0
Amp
QST: Motor FLA
01
1
0 Amp
QST: Motor FLA
01
3
0 Amp
QST: Motor FLA
01 30 Amp
RTD Lockout
RTD## = Sort
Summary of Contents for RediStart MX3 Series
Page 9: ...1 Introduction 1...
Page 15: ...2 Technical Specifications 7...
Page 35: ...3 Installation 27...
Page 61: ...4 Keypad Operation 53...
Page 71: ...5 Parameter Groups 63...
Page 79: ...6 Parameter Description 71...
Page 145: ...7 Theory of Operation 137...
Page 188: ...NOTES 180 7 THEORY OF OPERATION...
Page 189: ...8 Troubleshooting Maintenance 181...
Page 208: ...NOTES 200 8 TROUBLESHOOTING MAINTENANCE...
Page 209: ...Appendices 201...
Page 237: ...Publication History Revision Date ECO 00 12 15 06 Initial Release...