CT Ratio
FUN 03
LCD Display
Range
72:1, 96:1, 144:1, 288:1, 864:1, 2640:1, 3900:1, 5760:1, 8000:1, 14400:1, 28800:1,
50:5, 150:5, 250:5, 800:5, 2000:5, 5000:5
(Default 288:1)
Description
The CT Ratio parameter must be set to match the CTs (current transformers) supplied with the starter. This
allows the starter to properly calculate the current supplied to the motor.
Only Benshaw supplied CTs can be used on the starter. The CTs are custom 0.2 amp secondary CTs
specifically designed for use on the MX
3
starter. The CT ratio is then normalized to a 1A secondary value.
The supplied CT ratio can be confirmed by reading the part number on the CT label. The part number is of
the form BICTxxx1M, where xxx is the CT primary and the 1 indicates the normalized 1 amp.
z
NOTE:
It is very important that the CT ratio is set correctly. Otherwise, many starter functions will not
operate correctly.
Input Phase Sensitivity
FUN 04
LCD Display
LCD
Description
Range
Insensitive
Runs with any three phase sequence.
(Default)
ABC
Only runs with ABC phase sequence.
CBA
Only runs with CBA phase sequence.
Single phase
Single Phase.
Description
The Phase Order parameter sets the phase sensitivity of the starter. This can be used to protect the motor from
a possible change in the incoming phase sequence. If the incoming phase sequence does not match the set
phase rotation, the starter displays an alarm while stopped and faults if a start is attempted.
Rated RMS Voltage
FUN 05
LCD Display
Range
100, 110, 120, 200, 208, 220, 230, 240, 350, 380, 400, 415, 440, 460, 480, 500, 525, 575, 600, 660, 690, 800,
1000, 1140, 2200, 2300, 2400, 3300, 4160, 4600, 4800, 6000, 6600, 6900, 10.00K, 11.00K, 11.50K, 12.00K,
12.47K, 13.20K, 13.80K
(Default 480)
Description
The Rated Voltage parameter sets the line voltage that is used when the starter performs Over and Under line
voltage calculations. This value is the supply voltage, NOT the motor utilization voltage.
z
NOTE:
Settings above 1140V are for medium voltage applications.
z
NOTE:
The rated RMS voltage must be set properly in order for the starter to operate properly.
126
6 - PARAMETER DESCRIPTION
FUN:
CT Ratio
03
288:1
FUN: Phase Order
04
Insensitive
FUN: Rated Volts
05
480
Vlt
Summary of Contents for RediStart MX3 Series
Page 9: ...1 Introduction 1...
Page 15: ...2 Technical Specifications 7...
Page 35: ...3 Installation 27...
Page 61: ...4 Keypad Operation 53...
Page 71: ...5 Parameter Groups 63...
Page 79: ...6 Parameter Description 71...
Page 145: ...7 Theory of Operation 137...
Page 188: ...NOTES 180 7 THEORY OF OPERATION...
Page 189: ...8 Troubleshooting Maintenance 181...
Page 208: ...NOTES 200 8 TROUBLESHOOTING MAINTENANCE...
Page 209: ...Appendices 201...
Page 237: ...Publication History Revision Date ECO 00 12 15 06 Initial Release...