![BENSHAW RediStart MX3 Series User Manual Download Page 222](http://html1.mh-extra.com/html/benshaw/redistart-mx3-series/redistart-mx3-series_user-manual_2735259222.webp)
214
APPENDIX F - MODBUS REGISTER MAP
Absolute Register Address
Description
Range
Units
30143/40143
Rated RMS Voltage
0:
100
1:
110
2:
120
3:
200
4:
208
5:
220
6:
230
7:
240
8:
350
9:
380
10: 400
11: 415
12: 440
13: 460
14: 480
15: 500
16: 525
17: 575
18: 600
19: 660
20: 690
21: 800
22: 1000
23: 1140
24: 2200
25: 2300
26: 2400
27: 3300
28: 4160
29: 4600
30: 4800
31: 6000
32: 6600
33: 6900
34: 10000
35: 11000
36: 11500
37: 12000
38: 12470
39: 13200
40: 13800
Vrms
30144/40144
Input Phase Sensitivity
0:
Ins
1:
ABC
2:
CBA
3:
SPH
–
30145/40145
Motor Rated Power Factor
1 – 100
–
30146/40146
Overcurrent Enable
0:
Disabled
1:
Enabled
–
30147/40147
Overcurrent Level
50 – 800
% FLA
30148/40148
Overcurrent Delay Time Enable
0:
Disabled
1:
Enabled
–
30149/40149
Overcurrent Delay Time
1 – 900
100 mSec
30150/40150
Undercurrent Trip Enable
0:
Disabled
1:
Enabled
–
30151/40151
Undercurrent Trip Level
5 – 100
% FLA
30152/40152
Undercurrent Trip Delay Time Enable
0:
Disabled
1:
Enabled
–
30153/40153
Undercurrent Trip Delay Time
1 – 900
100 mSec
30154/40154
Current Imbalance Trip Enable
0:
Disabled
1:
Enabled
–
30155/40155
Current Imbalance Trip Level
5 – 40
%
Summary of Contents for RediStart MX3 Series
Page 9: ...1 Introduction 1...
Page 15: ...2 Technical Specifications 7...
Page 35: ...3 Installation 27...
Page 61: ...4 Keypad Operation 53...
Page 71: ...5 Parameter Groups 63...
Page 79: ...6 Parameter Description 71...
Page 145: ...7 Theory of Operation 137...
Page 188: ...NOTES 180 7 THEORY OF OPERATION...
Page 189: ...8 Troubleshooting Maintenance 181...
Page 208: ...NOTES 200 8 TROUBLESHOOTING MAINTENANCE...
Page 209: ...Appendices 201...
Page 237: ...Publication History Revision Date ECO 00 12 15 06 Initial Release...