6 - PARAMETER DESCRIPTION
Jump to Parameter
RTD 00
LCD Display
Description
By changing the value of this parameter and pressing [ENTER], you can jump directly to any parameter
within the group.
RTD Module #1 Address
RTD 01
LCD Display
Range
Off, 16 to 23
(Default Off)
Description
The module #1 address parameter has to be set to the Modbus address of the first RTD module attached to the
soft-starter. The address of the RTD module can be verified by checking the rotary switch on the top of the
RTD module.
RTD Module #2 Address
RTD 02
LCD Display
Range
Off, 16 to 23
(Default Off)
Description
The module #2 address parameter has to be set to the Modbus address of the second RTD module attached to
the soft-starter. The address of the RTD module can be verified by checking the rotary switch on the top of
the RTD module. Ensure that module #2 is not set to the same address as module #1.
RTD Group
RTD 03 - RTD 18
LCD Display
(? = RTD number)
(?? = menu index number)
LCD
Description
Range
Off
RTD channel not read.
Stator
RTD included in Stator metering group.
Bearing
RTD included in Bearing metering group.
Other
RTD acts independently.
RTD: RTDMod1 Addr
01
Off
RTD: RTDMod2 Addr
02
Off
RTD: RTD 1 Group
03
Off
RTD: RTD ? Group
??
Off
RTD: Jump Code
00
1
Summary of Contents for RediStart MX3 Series
Page 9: ...1 Introduction 1...
Page 15: ...2 Technical Specifications 7...
Page 35: ...3 Installation 27...
Page 61: ...4 Keypad Operation 53...
Page 71: ...5 Parameter Groups 63...
Page 79: ...6 Parameter Description 71...
Page 145: ...7 Theory of Operation 137...
Page 188: ...NOTES 180 7 THEORY OF OPERATION...
Page 189: ...8 Troubleshooting Maintenance 181...
Page 208: ...NOTES 200 8 TROUBLESHOOTING MAINTENANCE...
Page 209: ...Appendices 201...
Page 237: ...Publication History Revision Date ECO 00 12 15 06 Initial Release...