Stator Trip Level
RTD 22
LCD Display
Range
1 – 200
o
C
(Default 200
o
C)
Description
This parameter sets the stator trip temperature when a trip will occur. Fault delay time is 1 second.
Bearing Trip Level
RTD 23
LCD Display
Range
1 – 200
o
C
(Default 200
o
C)
Description
This parameter sets the bearing trip temperature when a trip will occur. Fault delay time is 1 second.
z
NOTE:
Consult motor manufacturer.
Other Trip Level
RTD 24
LCD Display
Range
1 – 200
o
C
(Default 200
o
C)
Description
This parameter sets the other trip temperature when a trip will occur. Fault delay time is 1 second.
122
6 - PARAMETER DESCRIPTION
RTD: Bearing Trip
23
200 C
RTD: Other Trip
24
200 C
RTD: Stator Trip
22
200 C