Once DC Braking is stopped due to a digital input state change, no further DC braking will take place and the starter will return to the
idle state.
7.5.8
Use of Optional Hall Effect Current Sensor
The Hall Effect Current Sensor should be located on Phase 1 of the motor output wiring. The sensor should be located so that the sensor
measures both the applied DC current from the starter as well as the freewheel current. The sensor is connected to the analog input of the
MX
3
card along with a burden resistor. The analog input must be set to be a 0-10V voltage input for correct operation. The sensor
scaling and burden resistance are factory selected. Please consult factory if changes to either the sensor scaling or burden resistance is
required.
z
NOTE:
Hall effect current sensor must be used when load inertia exceeds motor manufactures recommended specifications.