44
3 - INSTALLATION
Control Wiring
3.11
Control Wiring
3.11.1
Control Power
The 120VAC control power is supplied to TB1. The connections are as follows:
1 - Ground
2 - Neutral
3 - Neutral
4 - Line (120VAC)
5 - Line (120VAC)
3.11.2
Output Relays
TB2 is for output relays R1, R2 and R3. These relays connect as follows:
1 - NO1: Relay 1 normally open
2 - RC1: Relay 1 common
3 - NC1: Relay 1 normally closed
4 - NO2: Relay 2 normally open
5 - RC2: Relay 2 common
6 - NC2: Relay 2 normally closed
7 - NO3: Relay 3 normally open
8 - RC3: Relay 3 common
9 - NC3: Relay 3 normally closed
Terminal block J3 is for output relays R4, R5 and R6. These relays connect as follows:
1 - R4A: Relay 4 common
2 - R4B: Relay 4 open
3 - R5A: Relay 5 common
4 - R5B: Relay 5 open
5 - R6A: Relay 6 common
6 - R6B: Relay 6 open
See Also
Relay Output Configuration (I/O 10-15) on page 112.
120VAC LIVE
120VAC NEUTRAL
TB1
Figure 19: Control Power Wiring Example
120VAC LIVE
120VAC NEUTRAL
TRIP
TRIP PILOT LIGHT
(RELAY 1 SET TO FLFS - FAULT FAILSAFE)
120VAC LIVE
120VAC NEUTRAL
STOP
RUN & STOPPED PILOT LIGHT
(RELAY 2 SET TO RUN)
RUN
TB2
TB2
Figure 20: Relay Wiring Examples
Summary of Contents for RediStart MX3 Series
Page 9: ...1 Introduction 1...
Page 15: ...2 Technical Specifications 7...
Page 35: ...3 Installation 27...
Page 61: ...4 Keypad Operation 53...
Page 71: ...5 Parameter Groups 63...
Page 79: ...6 Parameter Description 71...
Page 145: ...7 Theory of Operation 137...
Page 188: ...NOTES 180 7 THEORY OF OPERATION...
Page 189: ...8 Troubleshooting Maintenance 181...
Page 208: ...NOTES 200 8 TROUBLESHOOTING MAINTENANCE...
Page 209: ...Appendices 201...
Page 237: ...Publication History Revision Date ECO 00 12 15 06 Initial Release...