8.7.4
SCR Clamp
Below is an exploded view of a typical SCR clamp. Refer to the Clamp Parts List on page 199 for names of the parts being used.
SCR CLAMP PARTS
8.7.5
Tightening Clamp
Finger tighten the clamp. Ensure both bolts are tightened an equal amount so that the loader bar (item 1) is square in the heatsink.
Tighten the bolts equally in 1/8 turn increments until the indicator washer(s) (item 6), which are under the nut(s) in the center of the
loader bar, becomes loose indicating the clamp is tight. On the loader bars with two indicator washers, it may be necessary to tighten or
loosen one side of the clamp to get both indicator washers free.
8.7.6
Testing SCR
After the SCRs have been replaced, conduct the resistance test as defined in Section 8.5.
199
8 - TROUBLESHOOTING & MAINTENANCE
Item #
Quantity
Description
1
1
Loader Bar
2
2
Insulator cup
3
2
Bolt
4
2
Washer
5
2
Serrated nut (larger style clamp has 1
support bar)
6
1 or 2
Indicator Washer – Quantity dependant
on style of clamp
Summary of Contents for RediStart MX3 Series
Page 9: ...1 Introduction 1...
Page 15: ...2 Technical Specifications 7...
Page 35: ...3 Installation 27...
Page 61: ...4 Keypad Operation 53...
Page 71: ...5 Parameter Groups 63...
Page 79: ...6 Parameter Description 71...
Page 145: ...7 Theory of Operation 137...
Page 188: ...NOTES 180 7 THEORY OF OPERATION...
Page 189: ...8 Troubleshooting Maintenance 181...
Page 208: ...NOTES 200 8 TROUBLESHOOTING MAINTENANCE...
Page 209: ...Appendices 201...
Page 237: ...Publication History Revision Date ECO 00 12 15 06 Initial Release...