8 - TROUBLESHOOTING & MAINTENANCE
Fault Code
Description
Detailed Description of Fault / Possible Solutions
F10
Phase Rotation Error, not ABC
Input phase rotation is not ABC and Input Phase Sensitivity parameter (FUN04) is
set to ABC only.
Verify correct phase rotation of input power. Correct wiring if necessary.
Verify correct setting of Input Phase Sensitivity parameter (FUN04).
F11
Phase Rotation Error, not CBA
Input phase rotation is not CBA and Input Phase Sensitivity parameter (FUN04) is
set to CBA only.
Verify correct phase rotation of input power. Correct wiring if necessary.
Verify correct setting of Input Phase Sensitivity parameter (FUN04).
F12
Low Line Frequency
Line frequency below Under Freq Trip (PFN15).
Verify input line frequency.
If operating on a generator, check generator speed governor for malfunctions.
Check input supply for open fuses or open connections.
Line power quality problem / excessive line distortion.
F13
High Line Frequency
Line frequency above Over Freq Trip (PFN14).
Verify input line frequency.
If operating on a generator, check generator speed governor for malfunctions.
Line power quality problem / excessive line distortion.
F14
Input power not single phase
Three-phase power has been detected when the starter is expecting single-phase
power.
Verify that input power is single phase.
Verify that single-phase power is connected to the L1 and L2 inputs. Correct
wiring if necessary.
Verify that the SCR gate wires are properly connected to the MX
3
control card.
F15
Input power not three phase
Single-phase power has been detected when the starter is expecting three-phase
power.
Verify that input power is three phase. Correct wiring if necessary.
Verify that the SCR gate wires are properly connected to the MX
3
control card.
On medium voltage systems, verify wiring of the voltage feedback measurement
circuit.
F21
Low Line L1-L2
Low voltage below the Under voltage Trip Level parameter setting (PFN11) was
detected for longer than the Over/Under Voltage Trip delay time (PFN12).
Verify that the actual input voltage level is correct.
Verify that the Rated Voltage parameter (FUN05) is set correctly.
Check input supply for open fuses or open connections.
On medium voltage systems, verify wiring of the voltage measurement circuit.
F22
Low Line L2-L3
Low voltage below the Under voltage Trip Level parameter setting (PFN11) was
detected for longer than the Over/Under Voltage Trip delay time (PFN12).
Verify that the actual input voltage level is correct.
Verify that the Rated Voltage parameter (FUN05) is set correctly.
Check input supply for open fuses or open connections.
On medium voltage systems, verify wiring of the voltage feedback measurement
circuit.
Summary of Contents for RediStart MX3 Series
Page 9: ...1 Introduction 1...
Page 15: ...2 Technical Specifications 7...
Page 35: ...3 Installation 27...
Page 61: ...4 Keypad Operation 53...
Page 71: ...5 Parameter Groups 63...
Page 79: ...6 Parameter Description 71...
Page 145: ...7 Theory of Operation 137...
Page 188: ...NOTES 180 7 THEORY OF OPERATION...
Page 189: ...8 Troubleshooting Maintenance 181...
Page 208: ...NOTES 200 8 TROUBLESHOOTING MAINTENANCE...
Page 209: ...Appendices 201...
Page 237: ...Publication History Revision Date ECO 00 12 15 06 Initial Release...