![BENSHAW RediStart MX3 Series User Manual Download Page 231](http://html1.mh-extra.com/html/benshaw/redistart-mx3-series/redistart-mx3-series_user-manual_2735259231.webp)
Protection Function Group
223
APPENDIX G - PARAMETER TABLES
Group
LED
Display
Parameter
Setting Range
Units
Default
Page
Setting
CFN 22
P21
Brake Delay
DC Brake Delay
0.1 to 3.0
Seconds
0.2
89
CFN 23
P27
SSpd Speed
Slow Speed
Off, 1 – 40
%
Off
90
CFN 24
P28
SSpd Curr
Slow Speed Current Level
10 to 400
% FLA
100
90
CFN 25
P29
SSpd Timer
Slow Speed Timer
Off, 1 to 900
Seconds
10
91
CFN 26
P30
SSpd Kick Curr
Slow Speed Kick Level
Off, 100 to 800
% FLA
Off
91
CFN 27
P31
SSpd Kick T
Slow Speed Kick Time
0.1 to 10.0
Seconds
1.0
92
Group
LED
Display
Parameter
Setting Range
Units
Default
Page
Setting
PFN 00
Jump Code
Jump to parameter
1 - 35
1
PFN 01
P32
Over Cur Lvl
Over Current Trip Level
Off, 50 - 800
%FLA
Off
92
PFN 02
P33
Over Cur Time
Over Current Trip Delay Time
Off, 0.1 - 90.0
Seconds
0.1
93
PFN 03
P34
Undr Cur Lvl
Under Current Trip Level
Off, 5 - 100
%FLA
Off
93
PFN 04
P35
Undr Cur Time
Under Current Trip Delay Time
Off, 0.1 - 90.0
Seconds
0.1
94
PFN 05
P36
Cur Imbl Lvl
Current Imbalance Trip Level
Off, 5 - 40
%
15
94
PFN 06
Cur Imbl Time
Current Imbalance Trip Time
0.1 - 90
Seconds
10
95
PFN 07
P37
Resid GF Lvl
Residual Ground Fault Trip Level
Off, 5 - 100
%FLA
Off
96
PFN 08
ZS GF Lvl
Zero Sequence Ground Fault Trip
Level
Off, 1.0 - 25
Amps
Off
97
PFN 09
Gnd Flt Time
Ground Fault Trip Time
0.1 - 90.0
Seconds
3.0
98
PFN 10
P38
Over Vlt Lvl
Over Voltage Trip Level
Off, 1 - 40
%
Off
98
PFN 11
P39
Undr Vlt Lvl
Under Voltage Trip Level
Off, 1 - 40
%
Off
99
PFN 12
P40
Vlt Trip Time
Over/Under Voltage Trip Delay
Time
0.1 - 90.0
Seconds
0.1
99
PFN 13
Ph Loss Time
Phase Loss Trip Time
0.1 - 5.0
Seconds
0.2
100
PFN 14
Over Frq Lvl
Over Frequency Trip
24 - 72
Hz
72
100
PFN 15
Undr Frq Lvl
Under Frequency Trip
23 - 71
Hz
23
100
PFN 16
Frq Trip Time
Frequency Trip Time
0.1 - 90.0
Seconds
0.1
101
PFN 17
PF Lead Lvl
PF Lead Trip Level
Off, -0.80 lag to
+0.01 lead
Off
101
PFN 18
PF Lag Lvl
PF Lag Trip Level
Off, -0.01 lag to
+0.80 lead
Off
101
PFN 19
PF Trip Time
PF Trip Time
0.1 - 90.0
Seconds
10.0
101
PFN 20
Backspin Time
Backspin Timer
Off, 1 - 180
Minutes
Off
102
PFN 21
Time Btw St
Time Between Starts
Off, 1 - 180
Minutes
Off
102
PFN 22
Starts/Hour
Starts per Hour
Off, 1 - 6
Off
102
PFN 23
P41
Auto Reset
Auto Fault Reset Time
Off, 1 - 900
Seconds
Off
102
PFN 24
P42
Auto Rst Lim
Auto Fault Reset
Count Limit
Off, 1 - 10
Off
103
PFN 25
P43
Ctrl Flt En
Controlled Fault Stop
Off, On
On
103
PFN 26
Speed Sw Time
Speed Switch Trip Time
Off, 1 - 250
Seconds
Off
104
PFN 27
M PTC Time
Motor PTC Trip Time
Off, 1 - 5
Seconds
Off
104
PFN 28
P44
Indep S® OL
Independent Starting/Running
Overload
Off, On
Off
105
PFN 29
P45
Starting OL
Motor Overload Class Starting
Off, 1 - 40
10
106
PFN 30
Running OL
Motor Overload Class Running
Off, 1 - 40
10
106
PFN 31
P46
OL H© Ratio
Motor Overload Hot/Cold Ratio
0 - 99
%
60
107
Summary of Contents for RediStart MX3 Series
Page 9: ...1 Introduction 1...
Page 15: ...2 Technical Specifications 7...
Page 35: ...3 Installation 27...
Page 61: ...4 Keypad Operation 53...
Page 71: ...5 Parameter Groups 63...
Page 79: ...6 Parameter Description 71...
Page 145: ...7 Theory of Operation 137...
Page 188: ...NOTES 180 7 THEORY OF OPERATION...
Page 189: ...8 Troubleshooting Maintenance 181...
Page 208: ...NOTES 200 8 TROUBLESHOOTING MAINTENANCE...
Page 209: ...Appendices 201...
Page 237: ...Publication History Revision Date ECO 00 12 15 06 Initial Release...