RTD Bias Minimum Level
RTD 27
LCD Display
Range
0 – 198
o
C
(Default 40
o
C)
Description
Typically set to ambient conditions. (40
o
C)
See Also
RTD Biasing OL group in section 7.1.7 on page 143.
RTD Bias Midpoint Level
RTD 28
LCD Display
Range
1 – 199
o
C
(Default 130
o
C)
Description
Typically set at the rated motor running temperature.
z
NOTE:
Consult motor manufacturer for information.
See Also
RTD Biasing OL group in section 7.1.7, on page 143.
RTD Bias Maximum Level
RTD 29
LCD Display
Range
105 – 200
o
C
(Default 155
o
C)
Description
The stator insulation maximum temperature rating.
z
NOTE:
Consult motor manufacturer for information.
See Also
RTD Biasing OL group in section 7.1.7, on page 143.
124
6 - PARAMETER DESCRIPTION
RTD: RTD Bias Mid
28
130 C
RTD: RTD Bias Max
29
155 C
RTD: RTD Bias Min
27
40 C