![BENSHAW RediStart MX3 Series User Manual Download Page 126](http://html1.mh-extra.com/html/benshaw/redistart-mx3-series/redistart-mx3-series_user-manual_2735259126.webp)
118
6 - PARAMETER DESCRIPTION
Analog Output Offset
I/O 23
LCD Display
Range
0 – 99%
(Default 0%)
Description
The analog output signal can be offset using the Analog Output Offset parameter. A 50% offset outputs a
50% output (5V in the 10V case) when 0% is commanded. If the selected variable requests 100% output, the
span should be reduced to (100 minus offset) so that a 100% output request causes a 100% output voltage (x%
(100-x)%span)=100%.
z
NOTE:
For a 4-20mA output, set the Analog Output Span to 80% and the Analog Output Offset to 20%.
See Also
Analog Output Span parameter (I/O22) on page 117.
Inline Configuration
I/O 24
LCD Display
Range
Off, 0 – 10.0 seconds
(Default 3.0)
Description
The Inline Configuration parameter controls the behavior of the No Line warning, No Line fault, and the
Ready relay function.
If the Inline Configuration parameter is set to "Off", then the MX
3
assumes that there is no Inline contactor
and that line voltage should be present while stopped. If no line is detected, then a No Line alarm condition
exists and the ready condition does not exist. If a start is commanded, then a No Line fault is declared.
If the Inline Configuration parameter is set to a "time delay", then the MX
3
assumes that there is an Inline
contactor and that line voltage need not be present while stopped. If no line is detected, then the No Line
alarm condition does not exist and the ready condition does exist. If a start is commanded and there is no
detected line voltage for the time period defined by this parameter, then a “noL” (No Line) fault is declared.
In order to control an inline contactor, program a relay as a Run relay.
z
NOTE:
This fault is different than over/under voltage since it detects the presence of NO line.
See Also
Relay Output Configuration parameters (I/O 10-15) on page 112.
Bypass Feedback Time
I/O 25
LCD Display
Range
0.1 – 5.0 seconds
(Default 2.0)
Description
The starter contains a built in dedicated bypass feedback input that is enabled when the dedicated stack relay
is factory programmed to "bypass". The programmable inputs DI 1, DI 2, DI 3, DI4, DI5, DI6, DI7 or DI8
may also be used to monitor an auxiliary contact from the bypass contactor(s) or in the case of a wye-delta
starter the 2M contactor. The digital input is expected to be in the same state as the UTS relay. If it is not, the
MX
3
trips on Fault 48 (Bypass Fault).
The Bypass Confirmation input must be different from the UTS relay for the time period specified by this
parameter before a fault is declared. There is no alarm associated with this fault.
I/O: Aout Offset
23
0 %
I/O: Inline Confg
24
3.0 sec
I/O: Bpas Fbk Tim
25
2.0 sec
Summary of Contents for RediStart MX3 Series
Page 9: ...1 Introduction 1...
Page 15: ...2 Technical Specifications 7...
Page 35: ...3 Installation 27...
Page 61: ...4 Keypad Operation 53...
Page 71: ...5 Parameter Groups 63...
Page 79: ...6 Parameter Description 71...
Page 145: ...7 Theory of Operation 137...
Page 188: ...NOTES 180 7 THEORY OF OPERATION...
Page 189: ...8 Troubleshooting Maintenance 181...
Page 208: ...NOTES 200 8 TROUBLESHOOTING MAINTENANCE...
Page 209: ...Appendices 201...
Page 237: ...Publication History Revision Date ECO 00 12 15 06 Initial Release...