93
6 - PARAMETER DESCRIPTION
Description
If the MX
3
detects a one cycle, average current that is greater than the level defined, an over current alarm
condition exists and any relays programmed as alarm will energize. The over current timer starts a delay time.
If the over current still exists when the delay timer expires, the starter Over Current Trips (F31) any relay
programmed as fault relay changes state.
The Over Current Trip is only active in the UTS state, Energy Saver state, Current follower or while in the
Phase Control mode.
A relay can be programmed to change state when an over current alarm condition is detected.
See Also
Over Current Time parameter (PFN02) on page 93.
Auto Reset parameter (PFN23) on page 102.
Controlled Fault Stop Enable parameter (PFN25) on page 103.
Relay Output Configuration parameters (I/O 10 - 15) on page 112.
Over Current Trip Delay Time
PFN 02
LCD Display
Range
Off, 0.1 – 90.0 seconds
(Default 0.1)
Description
The Over Current Trip Delay Time parameter sets the period of time that the motor current must be greater
than the Over Current Trip Level (PFN01) parameter before an over current fault and trip occurs.
If "Off" is selected, the over current timer does not operate and the starter does not trip. It energizes any relay
set to Over current until the current drops or the starter trips on an overload.
A shear pin function can be implemented by setting the delay to its minimum value.
See Also
Over Current Level parameter (PFN01) on page 92.
Auto Reset parameter (PFN23) on page102.
Controlled Fault Stop Enable parameter (PFN25) on page 103.
Relay Output Configuration parameters (I/O 10 - 15) on page 112.
Under Current Trip Level
PFN 03
LCD Display
Range
Off, 5 – 100 % of FLA
(Default Off)
PFN: Over Cur Tim
02
0.1 sec
PFN: Undr Cur Lvl
03
Off
Time
Alarm
Condition
Fault
Trip
% Current
Over Current Trip
Delay Time
PFN 02
Over Cur Level
PFN 01
Motor FLA
QST 01
Summary of Contents for RediStart MX3 Series
Page 9: ...1 Introduction 1...
Page 15: ...2 Technical Specifications 7...
Page 35: ...3 Installation 27...
Page 61: ...4 Keypad Operation 53...
Page 71: ...5 Parameter Groups 63...
Page 79: ...6 Parameter Description 71...
Page 145: ...7 Theory of Operation 137...
Page 188: ...NOTES 180 7 THEORY OF OPERATION...
Page 189: ...8 Troubleshooting Maintenance 181...
Page 208: ...NOTES 200 8 TROUBLESHOOTING MAINTENANCE...
Page 209: ...Appendices 201...
Page 237: ...Publication History Revision Date ECO 00 12 15 06 Initial Release...