8 - TROUBLESHOOTING & MAINTENANCE
Fault Code
Description
Detailed Description of Fault / Possible Solutions
F23
Low Line L3-L1
Low voltage below the Under voltage Trip Level parameter setting (PFN11) was
detected for longer than the Over/Under Voltage Trip delay time (PFN12).
Verify that the actual input voltage level is correct.
Verify that the Rated Voltage parameter (FUN05) is set correctly.
Check input supply for open fuses or open connections.
On medium voltage systems, verify wiring of the voltage feedback measurement
circuit.
F24
High Line L1-L2
High voltage above the Over voltage Trip Level parameter setting (PFN10) was
detected for longer than the Over/Under Voltage Trip delay time (PFN12).
Verify that the actual input voltage level is correct.
Verify that the Rated Voltage parameter (FUN05) is set correctly.
Line power quality problems/ excessive line distortions.
F25
High Line L2-L3
High voltage above the Over voltage Trip Level parameter setting (PFN10) was
detected for longer than the Over/Under Voltage Trip delay time (PFN12).
Verify that the actual input voltage level is correct.
Verify that the Rated Voltage parameter (FUN05) is set correctly.
Line power quality problems/ excessive line distortions.
F26
High Line L3-L1
High voltage above the Over voltage Trip Level parameter setting (PFN10) was
detected for longer than the Over/Under Voltage Trip delay time (PFN12).
Verify that the actual input voltage level is correct.
Verify that the Rated Voltage parameter (FUN05) is set correctly.
Line power quality problems/ excessive line distortions.
F27
Phase Loss
The MX
3
has detected the loss of one or more input or output phases when the
starter was running. Can also be caused by line power dropouts.
Check input supply for open fuses.
Check power supply wiring for open or intermittent connections.
Check motor wiring for open or intermittent connections.
On medium voltage systems, verify wiring of the voltage feedback measurement
circuit.
Check Gate and Cathode connections to MX
3
card.
F28
No Line
No input voltage was detected for longer than the Inline Configuration time delay
parameter setting ( I/O24) when a start command was given to the starter.
If an inline contactor is being used, verify that the setting of the Inline
Configuration time delay parameter (I/O24) allows enough time for the inline
contactor to completely close.
Check input supply for open disconnects, open fuses, open circuit breakers or
disconnected wiring.
Verify that the SCR gate wires are properly connected to the MX
3
control card.
On medium voltage systems, verify wiring of the voltage feedback measurement
circuit.
F29
PORT Timeout
PORT fault timer timed out before line power returned.
Extend PORT fault time parameter (FUN10) if possible.
F30
I.O.C.
(Instantaneous Over current)
During operation, the MX
3
detected a very high level of current in one or more
phases.
Check motor wiring for short circuits or ground faults.
Check motor for short circuits or ground faults.
Check if power factor or surge capacitors are installed on the motor side of the
starter.
Verify that the motor FLA (QST01) and CT ratio (FUN03) settings are correct.
Summary of Contents for RediStart MX3 Series
Page 9: ...1 Introduction 1...
Page 15: ...2 Technical Specifications 7...
Page 35: ...3 Installation 27...
Page 61: ...4 Keypad Operation 53...
Page 71: ...5 Parameter Groups 63...
Page 79: ...6 Parameter Description 71...
Page 145: ...7 Theory of Operation 137...
Page 188: ...NOTES 180 7 THEORY OF OPERATION...
Page 189: ...8 Troubleshooting Maintenance 181...
Page 208: ...NOTES 200 8 TROUBLESHOOTING MAINTENANCE...
Page 209: ...Appendices 201...
Page 237: ...Publication History Revision Date ECO 00 12 15 06 Initial Release...