Description
The Tachometer Loss Time is the allowable time the starter will operate when a tachometer signal is lost. If
the signal is lost, the starter will perform the action set by the Tach Loss Action parameter.
z
NOTE:
Nuisance tachometer loss faults at start can be prevented by setting the initial current parameter to
a value that allows the motor to begin rotating soon after a start is commanded.
Tachometer Loss Action
FUN 15
LCD Display
LCD
Description
Range
Fault
The starter will shutdown and indicate a tachometer loss fault.
Current Acceleration
If the tachometer signal is lost the starter will fault. However the
start mode parameter will be set to Current control acceleration so
that when the fault is reset the starter will start in Current control
mode.
TruTorque Accel
If the tachometer signal is lost the starter will fault. However the
start mode parameter will be set to TruTorque control acceleration so
that when the fault is reset the starter will start in Current control
mode.
KW (Power)
If the tachometer signal is lost the starter will fault. However the
start mode parameter will be set to KW (Power) so that when the fault is
reset the starter will start in Current control mode.
Description
If the tachometer detects the feedback signal is not valid one of the above actions will be taken depending on
the value of the Tach Loss Action user parameter.
Communication Address
FUN 16
LCD Display
Range
1 – 247
(Default 1)
Description
The Communication Address parameter sets the starter’s address for Modbus communications.
See Also
Local Source parameter (QST04) on page 74.
Remote Source parameter (QST05) on page 74.
Communication Baud Rate parameter (FUN17) on page 131.
Communication Timeout parameter (FUN18) on page 132.
Communication Byte Framing parameter (FUN19) on page 132.
Communication Baud Rate
FUN 17
LCD Display
Range
1200, 2400, 4800, 9600, 19200 bps
(Default 19200)
Description
The Communication Baud Rate parameter sets the baud rate for Modbus communications.
131
6 - PARAMETER DESCRIPTION
FUN: Com Drop #
16
1
FUN: Com Baudrate
17
19200
FUN: Tach Los Act
15
Fault
Summary of Contents for RediStart MX3 Series
Page 9: ...1 Introduction 1...
Page 15: ...2 Technical Specifications 7...
Page 35: ...3 Installation 27...
Page 61: ...4 Keypad Operation 53...
Page 71: ...5 Parameter Groups 63...
Page 79: ...6 Parameter Description 71...
Page 145: ...7 Theory of Operation 137...
Page 188: ...NOTES 180 7 THEORY OF OPERATION...
Page 189: ...8 Troubleshooting Maintenance 181...
Page 208: ...NOTES 200 8 TROUBLESHOOTING MAINTENANCE...
Page 209: ...Appendices 201...
Page 237: ...Publication History Revision Date ECO 00 12 15 06 Initial Release...