See Also
Digital Input Configuration parameters (I/O 01-08) on page 111.
Theory of Operation section 7.8, Wye-Delta Operation on page 168.
Keypad Stop Disable
I/O 26
LCD Display
LCD
Description
Range
Disabled Keypad Stop does not stop the starter.
Enabled
Keypad Stop does stop the starter.
(Default)
Description
If “Disabled”
When this parameter is set to "Disabled", the keypad [STOP] button is de-activated. This should be done with
caution, as the [STOP] will not stop the starter.
If the keypad is selected as local or remote control sources, the [STOP] key cannot be disabled.
If “Enabled”
When this parameter is set to "Enabled", the keypad stop button is enabled and stops the starter regardless of
the selected control source (keypad, terminal or serial).
See Also
Local Source parameter (QST04) on page 74.
Remote Source parameter (QST05) on page 74.
Auto Start Selection
I/O 27
LCD Display
LCD
Description
Range
Disabled
When Disabled, the Start input must always transition from low to high
for a start to occur.
(Default)
Power
When set to Power, a start will occur if the Start input is high while
control power is applied.
Fault
When set to Fault, a start will occur if the Start input is high when a
fault is reset.
Power, Fault
When set to Power and Fault, a start will occur if the Start input is
high while control power is applied, and a start will occur if the Start
input is high when a fault is reset.
Description
The Auto Start Selection parameter determines whether or not a transition from low to high is required on the
Start input for a start to occur after either a power up or a fault reset. This applies to lockout conditions being
cleared as well. The behavior for a lockout clearing is the same as for a fault being reset.
119
6 - PARAMETER DESCRIPTION
I/O: Keypad Stop
26 Enabled
I/O: Auto Start
27 Disabled
Summary of Contents for RediStart MX3 Series
Page 9: ...1 Introduction 1...
Page 15: ...2 Technical Specifications 7...
Page 35: ...3 Installation 27...
Page 61: ...4 Keypad Operation 53...
Page 71: ...5 Parameter Groups 63...
Page 79: ...6 Parameter Description 71...
Page 145: ...7 Theory of Operation 137...
Page 188: ...NOTES 180 7 THEORY OF OPERATION...
Page 189: ...8 Troubleshooting Maintenance 181...
Page 208: ...NOTES 200 8 TROUBLESHOOTING MAINTENANCE...
Page 209: ...Appendices 201...
Page 237: ...Publication History Revision Date ECO 00 12 15 06 Initial Release...