9
2 - TECHNICAL SPECIFICATIONS
Function
Terminal
Block
Terminal Number
Description
Digital Inputs
TB3
1: Start
2: DI1
3: DI2
4: DI3
5: Common
120VAC digital input
2500V optical isolation
4mA current draw
Off: 0-35VAC
On: 60-120VAC
Digital Inputs
J6
1: DI4
2: DI5
3: DI6
4: DI7
5: DI8
6: Common
120VAC digital input
2500V optical isolation
4mA current draw
Off: 0-35VAC
On: 60-120VAC
Serial Comm
TB4
1: B+
2: A-
3: COM
Modbus RTU serial communication port.
RS-485 interface
19.2k baud maximum
2500V Isolation
Analog I/O
TB5
1: Ain Power
2: Ain +
3: Ain -
4: Common
5: Aout
6: Common
7: Shield
Input:
Voltage or Current
Voltage: 0-10VDC, 67K
W
impedance
Current: 0-20mA, 500
W
impedance
Output:
Voltage or Current
Voltage: 0-10VDC, 120mA maximum
Current: 0-20mA, 500
W
load maximum
PTC Thermistor Input
J7
1: Motor PTC
2: Motor PTC
Positive Temperature Coefficient Thermistor
- Trip resistance 3.5K, ± 300 Ohms.
- Reset resistance 1.65K, ± 150 Ohms.
- Open terminal voltage is 15V.
- PTC voltage at 4Kohms = 8.55V. (>7.5V)
- Response time adjustable between 1 and 5
seconds.
- Maximum cold resistance of PTC chain = 1500
Ohms.
Zero Sequence Ground
Fault
J15
1: CT input
2: CT input
Zero Sequence Ground Fault
CT Type: 50:0.025 (2000:1 ratio)
Measurement range: 0.1A - 25.0 Amps Accuracy : +/- 3%
Burden at 25Amps : 0.0089VA.
Display
RJ45
Door Mounted Display Connector
SCR
J6 to J11
1: Gate
2: Cathode
SCR gate Connections
Phase C.T.
J12
1: CT1+
2: CT1
3: CT2+
4: CT2
5: CT3+
6: CT3
Phase CT Connector
Wire Gauge
The terminals can support 1- 14 AWG wire or 2-16 AWG wires or smaller.
Torque Rating
The terminals on the control cards have a torque rating of 5.0-inch lb. or 0.56Nm. This MUST be
followed or damage will occur to the terminals.
z
NOTE:
Refer to Control Card Layouts starting on page 41.
Table 1: Terminals
Summary of Contents for RediStart MX3 Series
Page 9: ...1 Introduction 1...
Page 15: ...2 Technical Specifications 7...
Page 35: ...3 Installation 27...
Page 61: ...4 Keypad Operation 53...
Page 71: ...5 Parameter Groups 63...
Page 79: ...6 Parameter Description 71...
Page 145: ...7 Theory of Operation 137...
Page 188: ...NOTES 180 7 THEORY OF OPERATION...
Page 189: ...8 Troubleshooting Maintenance 181...
Page 208: ...NOTES 200 8 TROUBLESHOOTING MAINTENANCE...
Page 209: ...Appendices 201...
Page 237: ...Publication History Revision Date ECO 00 12 15 06 Initial Release...