Independent Starting/Running Overload parameter (PFN28) on page 105.
Motor Starting Overload Class parameter (PFN29) on page 106.
Motor Overload Hot/Cold Ratio parameter (PFN31) on page 107.
Motor Overload Cooling Time parameter (PFN32) on page 108.
Relay Output Configuration parameter (I/O 10-15) on page 112.
Theory of Operation section 7.1, Solid State Motor Overload Protection on page 138.
Motor Overload Hot/Cold Ratio
PFN 31
LCD Display
Range
0 – 99%
(Default 60%)
Description
The Motor Overload Hot/Cold Ratio parameter defines the steady state overload content (OL
ss
) that is reached
when the motor is running with a current less than full load current (FLA) * Service Factor (SF). This
provides for accurate motor overload protection during a “warm” start.
The steady state overload content is calculated by the following formula.
The rise or fall time for the overload to reach this steady state is defined by the Motor Overload Cooling Time
(PFN32) parameter.
The default value of 60% for Motor Overload Hot/Cold Ratio parameter is typical for most motors. A more
accurate value can be derived from the hot and cold locked rotor times that are available from most motor
manufacturers using the following formula.
z
NOTE
: Consult motor manufacturer data to determine the correct motor overload settings.
See Also
Independent Starting/Running Overload parameter (PFN28) on page 105.
Motor Running Overload Class parameter (PFN30) on page 106.
Motor Starting Overload Class parameter (PFN29) on page 106.
Motor Overload Cooling Time parameter (PFN32) on page 108.
Relay Output Configuration parameters (I/O 10-15) on page 112.
Theory of Operation section 7.1.6, Hot/Cold Motor Overload Compensation on page 141.
107
6 - PARAMETER DESCRIPTION
PFN: OL H/C Ratio
31
60 %
Factor
Derate
Imbalance
Current
1
FLA
Current
Ratio
H/C
OL
OL
ss
´
=
100%
x
Time
Rotor
Locked
Cold
Max
Time
Rotor
cked
Max Hot Lo
1
Ratio
H/C
OL
÷
ø
ö
ç
è
æ -
=
Summary of Contents for RediStart MX3 Series
Page 9: ...1 Introduction 1...
Page 15: ...2 Technical Specifications 7...
Page 35: ...3 Installation 27...
Page 61: ...4 Keypad Operation 53...
Page 71: ...5 Parameter Groups 63...
Page 79: ...6 Parameter Description 71...
Page 145: ...7 Theory of Operation 137...
Page 188: ...NOTES 180 7 THEORY OF OPERATION...
Page 189: ...8 Troubleshooting Maintenance 181...
Page 208: ...NOTES 200 8 TROUBLESHOOTING MAINTENANCE...
Page 209: ...Appendices 201...
Page 237: ...Publication History Revision Date ECO 00 12 15 06 Initial Release...