5.2.3
Protection Group
66
5 - PARAMETER GROUPS
Group
LED
Display
Parameter
Setting Range
Units
Default
Page
PFN 00
Jump Code
Jump to parameter
1 - 35
1
92
PFN 01
P32
Over Cur Lvl
Over Current Trip Level
Off, 50 - 800
%FLA
Off
92
PFN 02
P33
Over Cur Time
Over Current Trip Delay Time
Off, 0.1 - 90.0
Seconds
0.1
93
PFN 03
P34
Undr Cur Lvl
Under Current Trip Level
Off, 5 - 100
%FLA
Off
93
PFN 04
P35
Undr Cur Time
Under Current Trip Delay Time
Off, 0.1 - 90.0
Seconds
0.1
94
PFN 05
P36
Cur Imbl Lvl
Current Imbalance Trip Level
Off, 5 - 40
%
15
94
PFN 06
Cur Imbl Time
Current Imbalance Trip Time
0.1 - 90
Seconds
10
95
PFN 07
P37
Resid GF Lvl
Residual Ground Fault Trip Level
Off, 5 - 100
%FLA
Off
96
PFN 08
ZS GF Lvl
Zero Sequence Ground Fault Trip
Level
Off, 1.0 - 25
Amps
Off
97
PFN 09
Gnd Flt Time
Ground Fault Trip Time
0.1 - 90.0
Seconds
3.0
98
PFN 10
P38
Over Vlt Lvl
Over Voltage Trip Level
Off, 1 - 40
%
Off
98
PFN 11
P39
Undr Vlt Lvl
Under Voltage Trip Level
Off, 1 - 40
%
Off
99
PFN 12
P40
Vlt Trip Time
Over/Under Voltage Trip Delay
Time
0.1 - 90.0
Seconds
0.1
99
PFN 13
Ph Loss Time
Phase Loss Trip Time
0.1 - 5.0
Seconds
0.2
100
PFN 14
Over Frq Lvl
Over Frequency Trip Level
24 - 72
Hz
72
100
PFN 15
Undr Frq Lvl
Under Frequency Trip Level
23 - 71
Hz
23
100
PFN 16
Frq Trip Time
Frequency Trip Time
0.1 - 90.0
Seconds
0.1
101
PFN 17
PF Lead Lvl
PF Lead Trip Level
Off, -0.80 lag to +0.01
lead
Off
101
PFN 18
PF Lag Lvl
PF Lag Trip Level
Off, -0.01 lag to +0.80
lead
Off
101
PFN 19
PF Trip Time
PF Trip Time
0.1 - 90.0
Seconds
10.0
101
PFN 20
Backspin Time
Backspin Timer
Off, 1 - 180
Minutes
Off
102
PFN 21
Time Btw St
Time Between Starts
Off, 1 - 180
Minutes
Off
102
PFN 22
Starts/Hour
Starts per Hour
Off, 1 - 6
Off
102
PFN 23
P41
Auto Reset
Auto Fault Reset Time
Off, 1 - 900
Seconds
Off
102
PFN 24
P42
Auto Rst Lim
Auto Fault Reset Count Limit
Off, 1 - 10
Off
103
PFN 25
P43
Ctrl Flt En
Controlled Fault Stop
Off, On
On
103
PFN 26
Speed Sw Time
Speed Switch Trip Time
Off, 1 - 250
Seconds
Off
104
PFN 27
M PTC Time
Motor PTC Trip Time
Off, 1 - 5
Seconds
Off
104
PFN 28
P44
Indep S® OL
Independent Starting/Running
Overload
Off, On
Off
105
PFN 29
P45
Starting OL
Motor Overload Class Starting
Off, 1 - 40
10
106
PFN 30
Running OL
Motor Overload Class Running
Off, 1 - 40
10
106
PFN 31
P46
OL H© Ratio
Motor Overload Hot/Cold Ratio
0 - 99
%
60
107
PFN 32
P47
OL Cool Time
Motor Overload Cooling Time
1.0 - 999.9
Minutes
30
108
PFN 33
OL Alarm Lvl
Motor OL Alarm Level
1 - 100
%
90
108
PFN 34
OL Lock Lvl
Motor OL Lockout Level
1 - 99
%
15
109
PFN 35
OL Lock Calc
Motor OL Auto Lockout Level
Off, Auto
Off
110
Summary of Contents for RediStart MX3 Series
Page 9: ...1 Introduction 1...
Page 15: ...2 Technical Specifications 7...
Page 35: ...3 Installation 27...
Page 61: ...4 Keypad Operation 53...
Page 71: ...5 Parameter Groups 63...
Page 79: ...6 Parameter Description 71...
Page 145: ...7 Theory of Operation 137...
Page 188: ...NOTES 180 7 THEORY OF OPERATION...
Page 189: ...8 Troubleshooting Maintenance 181...
Page 208: ...NOTES 200 8 TROUBLESHOOTING MAINTENANCE...
Page 209: ...Appendices 201...
Page 237: ...Publication History Revision Date ECO 00 12 15 06 Initial Release...