Output definition – type Internal
(INPUT/OUTPUT, 2,
)
OUTPUT DEFINITION
State
:false
Output
:1
Trig.
:latched
Type
:Internal
Mode
:normal
Board
:17:VDS
continuous
Output
:1
unlogged
More
0. .9,
^V,
<>,
E,
X
Alarms: 0
Faults: 0
Cond.: 0
P: 1
SDZ
Return to Input/Output Menu
Page 109
Place cursor at TYPE
Select Type: INTERNAL and press
(Unlock memory!)
Use number 0..9 or
to select PC Board address and press
Use number 0..9 or
to select PC Board input number and press
Press [More
] to view Screen 2 of the outputs.
*See Common Facilities - All Output Types, Page 128 for a description of Output, State,
Trigger, Mode, Event and Text
The output number selects the relay provided on a printed circuit board within the FP2000
fire panel. In order to assign a physical relay, the PC Board
address
(
see Page 32 for
board addressing
) as well as the relay number on that board must be defined.
The FP2000 provides four programmable relays on the Sounder board (address 17) as
standard.
*See Hardware Configuration (Page 27) for installed PCB addresses.
This screen confirms the PC Board type when the board address is entered.
Trigger:
Latched/unlatched
Mode:
Normal/inverted
Continuous/pulse/pulsing
Unlogged/Logged
Text:
Allowed
* See Output Description in the Serial Communication Format