Output definition – type General
(INPUT/OUTPUT, 2,
)
OUTPUT DEFINITION
State
:false
Output
:1
Trig.
:latched
Type
:General
Mode
:normal
Fct.
:
continuous
Common Fire
unlogged
^V,
<>,
E,
X
Alarms: 0
Faults: 0
Cond.: 0
P: 1
SDZ
Return to Input/Output Menu
Page 109
Place cursor at TYPE
Select Type: GENERAL and press
(Unlock memory!)
Select the Function
*See Common Facilities - All Output Types, Page 128 for description of Output, State and
Text
General outputs cause the selected function to occur within the internal (system) of the
FP2000. The function description is assigned to an Output number.
The general functions provided are:
Common Fire
Common Fault
Common Condition
(Ext)ernal Fire
(Ext)ernal Fault
(Ext)ernal Supply Fault
Tamper Switch
Service Switch On
Sounder Disabled
Fire Brigade Disabled
Fault Routing Disabled
Fire Protection Disabled
Sounder Test
Fire Brigade Test
Fault Routing Test
Fire Protection Test
Trigger:
Latched or unlatched
Mode:
Normal only
Continuous only
Unlogged only
Text:
Not applicable
* See Output Description in the Serial Communication Format