Output definition – link to equipment
(INPUT/OUTPUT,
,
,
)
OUTPUT DEFINITION
Output
:1
Link
:SND
Mode
:Zone
Zone
:11
more
^V,
<>,
E,
X
Alarms: 0
Faults: 0
Cond.: 0
P: 1
SDZ
Return to Input/Output Menu
Page 109
Select Link: (SND, Fbrig, Fprot, Fltrt, Logic)
and press
(Unlock memory!) Enter Mode: (Zone/Area)
Select Zone or Area
Press [More
] to view Screen 1
The output can be linked to the Logic Table or to the standard output equipment
(Sounders [SND], Fire Brigade [Fbrig], Fire Protection [Fprot], Fault Routing [Fltrt])
When linked for logic, none of the equipment operations will affect the output. If the
output is linked to any of the above equipment it will operate together with the standard
equipment outputs provided.
Delay ON/OFF, Disable ON/OFF, Silence, Sound, Signal for a particular standard
equipment output (keys on FP2000 front panel) will affect these outputs. Evacuation
(Sound, Signal) is also affected by the mode of operation! (EN, NEN, EP and Vds).
Example 1
Output:
1
Link:
SND
Mode:
None
This is a common Sounder Output.
:
In EP mode the output switches ON.
In EN/NEN/Vds mode the output switches ON
only if it was silenced before.
:
The output is disabled.
:
The output is only switched after the Sounder
Delay has elapsed.
FIRE
:
The output switches ON.
SILENCE
:
The output switches OFF.
TEST
:
The output switches to Test Mode.
SOUND
DISABLE
DELAY ON/OFF