General setup and view (all types)
(DEVICE MENU, 1,
)
SCREEN 1
DEVICE SETUP
Address
:1/4
Status
:en
State
:NML
Zone
:1
Type
:OPT
Value
:38
Day Lvl
:3
PreLvl
:90
AlarmLvl
:110
more
^V,
<>,
E,
X
Alarms: 0
Faults: 0
Cond.: 0
P: 1
SDZ
Return to Device Menu
Page 78
Select field to be changed
Enter number 0..9 or
to change the data (Unlock memory!)
Confirm entry
Press [More
] to view additional device data (Screen 2)
*See Page 78 for the particular device type
For Device Text Fields (2 lines x 40 characters):
Use
to obtain the text line to be changed
Press
(Unlock memory!)
Use
to toggle between alpha and numeric text Press the alpha/numeric button
required
Use
to move the cursor within the line
Press
ü
ü
when completed
*See Page 62 to CLEAR device data
*See Page 65 for DEFAULT device setup
Each addressable device requires certain parameters to be set before the fire panel can
properly function. In addition to these parameters the status and statistics of each device
can be viewed on two screens. The [More
] button toggles between these two
screens.
Screen 1
is common to all devices with the exception of smoke and heat detectors that
have alarm level and day level settings. The
Screen 2
display is dependent on the device
type and is individually described on the following pages.
Setup parameters are best set as a group by using upload/download from a computer. A
default setup can also be obtained from the System Menus.