CL devices
(COMMUNICATION MENU, 4,
)
CL DEVICES
Panel
:0
Inputs
:0
Mode
:dis
Outputs
:0
0. . 9,
^V,
<>,
E,
X
Alarms: 0
Faults: 1
Cond.: 0
P: 1
FDZ
Return to Communication Menu
Page 37
Select field to be changed
Enter number 0..9 or
to change panel field
Select mode
Confirm entry (Unlock memory!)
Current Loop Devices:
All fireman’s panels connected to the current loop of the FP2000 fire panel are enabled
with this menu. Each fireman’s panel must have a unique address (
see FM800
Installation, Configuration & Detailed Operation Manual or FR800 Installation,
Configuration & Detailed Operation Manual
. Fireman’s panels that are enabled are
checked for communication, and a fault warning will occur in the event of a failure.
Mode:
The fireman’s panel can be assigned as Zone, Device, I/O or Area.
(See also CL Devices
Menu under Input/Output Menu, page 109)
.
Input and Output:
Display the number of inputs/outputs available on the fireman’s panel. (Communication
between the two systems must of course be established for the panel to acquire this
information.)