Common facilities – all output types
* See Output Description in the Serial Communication Format
Output:
number
Enter number or use
to view/change the existing defined
outputs, or create a new output. Each output required for the I/O
logic system must be defined by a unique output number.
Unused
outputs have type None. The maximum number of outputs (default
100) may be set in Memory Allocation (Page 33).
Type:
type
Output numbers are set true or false by logic. The action of the
output number is defined in the following types.
None
no output defined (default)
General
Page 131
Zone
Page 132
Area
Page 133
Internal
Page 134
Device Output
Page 135
Supervised Internal
Page 136
Supervised Device Output
Page 137
Network
Page 138
Current Loop Device
Page 139
Supervised Current Loop Device
Page 140
Event
Page 141
Action
Page 142
Fct:
function
The functions available depend on the output type selected. Refer
to the page of the specific function for further details.
State:
true/false
This view field shows the state of the output. The output state is set
by logic and conditioned by the Trigger and Mode of the output
definition.
Trig:
latched/unlatched
Latched
The output state, once switched true, will remain true until the fire
panel is
reset
even though the output conditions may become false
before the reset.
Mode:
normal/inverted
•
Normal
The output device is active when the output state is true.
•
Inverted
The output device is active when the output state is false.
continuous/pulse/pulsing