Input definition – type Internal
(INPUT/OUTPUT, 1,
)
INPUT DEFINITION
State
:false
Input
:1
Trig.
:latched
Type
:Internal
Mode
:active
Board
:24:FEP
continuous
Input
:1
Event
unlogged
0. .9,
^V,
<>,
E,
X
Alarms: 0
Faults: 0
Cond.: 0
P: 1
SDZ
Return to Input/Output Menu
Page 109
Place cursor at TYPE
Select Type: INTERNAL and press
(Unlock memory!)
Use number 0..9 or
to select PC Board address and press
Use number 0..9 or
to select PC Board input number and press
*See Common Facilities - All Input Types, Page 111 for a description of Input, State,
Trigger, Mode, Event and Text
The input number selected is assigned to a physical electrical input provided on a printed
circuit board within the FP2000 fire panel. In order to assign a physical input, the PC
Board
address
(
see Page 32 for board addressing
) as well as the input number on that
board must be defined.
For example:
the FP2000 provides four inputs on the FEP board
(address 24) as standard.
This screen confirms the PC Board type when the board address is entered.
Trigger:
Latched/Unlatched
Mode:
Passive/Active/Open/Short/Active1/Abnormal
Continuous/Pulse
Event:
Unlogged/Logged/Fire/Fault/Condition
Text:
Allowed
* See Input Description in the Serial Communication Format