Manual Call Point
(DEVICE MENU, 1,
,
)
SCREEN 2
DEVICE SETUP
ClrStat
Address
:1/2
Status
:en
State
:NML
CommQlt :100%
FldType
:MCP
FldDt
:32 ARI
TestVal
:225
Alarms
:0
more
0. .9,
^V,
<>,
E,
X
Alarms: 0
Faults: 0
Cond.: 0
P: 1
SDZ
Return to Device Menu
Page 78
Select field to be changed
Enter number 0..9 or
to change data
Confirm entry
Press [More
] to view Screen 1 of the device
The above screen is produced for manual call points, call point warning, call point
monitors, gas unit call points, as well as Mini Switch Monitoring Units with Interrupt in
order to view the device status and statistics.
Only two parameters can be changed on this screen:
Address:
Loop/address - Select a different device
ClrStat:
Clear the statistics of
this
device.
*See Clear Device Statistics, Page 162 to clear all devices on a loop.
The parameters that can be viewed are:
Status:
Enabled, Disabled or Soak: Shows if the device is currently
active or not. This can be changed on Screen 1 of the device
(
Page 79
).
State:
The latched alarm or fault state of the device.
*See Screen 1
(Page 79).
CommQlt:
Communication Quality: The number of correct replies from the
device as a percentage of the total number of polls to the
device. Communication quality is updated every 20 minutes
except when the device is being
viewed
, in which case it is
updated once per minute.
FldType:
Field Type: The device type as seen by the fire panel.
*See
Page 80 for field type descriptions
.
FldDt:
The value returned by a manual call point is one of three:
16
-
Fault
32
-
Normal
128
-
Fire Alarm
The protocol being used to communicate to this device is also
displayed. They are: ARI
-
Aritech Series 2000