off
-
ICC off
Warning Pls.
-
ICC operating intermittently
Alarm Pls.
-
ICC operating intermittently
Alarm cont.
-
the ICC is continuously operating
-
Depending on the communications protocol, this device is not always available.
Monitor units
(DEVICE MENU, 1,
,
)
SCREEN 2
DEVICE SETUP
ClrStat
Address
:1/7
Status
:en
State
:NML
CommQlt :100%
FldType
:MON
Value
:32 S90
TestVal
:225
Alarms
:0
More
0. .9,
^V,
<>,
E,
X
Alarms: 0
Faults: 0
Cond.: 0
P: 1
SDZ
Return to Device Menu
Page 78
Select field to be changed
Enter number 0..9 or
to change data
Confirm entry
Press [More
] to view Screen 1 of the device
The above screen is produced for zone monitor units, control unit monitors, Switch
Monitor and the Switch Monitor Plus in order to view the device status and statistics.
-
Note that the field type can be either "MON" or "ZMU", depending on the communication
protocol.
Only two parameters can be changed on this screen:
Address:
Loop/address - Select a different device
ClrStat:
Clear the statistics of
this
device.
*See Clear Device Statistics Page 162 to clear all devices in a loop.
The parameters that can be viewed are:
Status:
Enabled, Disabled or Soak: Shows if the device is currently
active or not. This can be changed on Screen 1 of the device
(
Page 79)
.
State:
The latched alarm or fault state of the device.
*See Screen 1
(Page 79).
CommQlt:
Communication Quality: The number of correct replies from the
device as a percentage of the total number of polls to the
device. Communication quality is updated every 20 minutes