Output test
(TEST MENU, 3,
)
OUTPUT TEST
Sounder
:off
Fbrig
:off
Fltrt
:off
Fprot
:off
^V,
<>,
E,
X
Alarms: 0
Faults: 1
Cond.: 0
P: 1
SDZ
Return to Test Menu
Page 184
Select Sounder Test/FB Test
Toggle ON/OFF
Confirm entry
The Sounder, Fire Brigade, Fault Routing and Fire Protection, outputs can be tested. The
tested outputs are pulsed at once per second. This test remains active even if the user
exits the menu. The tests are cancelled by toggling to OFF.
The outputs pulsed by Sounder Test are:
•
the monitored Sounder output relay
•
any internal relays linked to Sounder in the Output Menu
•
all loop sounder circuit controllers set as a Device Output or Supervised Device
Output and linked to Sounder in the Output Menu
The outputs pulsed by Fire Brigade Test are similarly:
•
the monitored Fire Brigade output relay
•
any internal relays linked to Fire Brigade in the Output Menu
•
all loop sounder circuit controllers set as Device Output or Supervised Device Output
and linked to Fire Brigade in the Output Menu
The outputs pulsed by Fault Routing are:
•
the fault routing output relay
•
any internal relays linked to fault routing in the Output Menu
•
all loop sounder circuit controllers set as Device Output or Supervised Device Output
and linked to Fault Routing in the Output Menu
The outputs pulsed by Fire Protection are:
•
the fire protection output relay
•
any internal relays linked to fire protection in the Output Menu
•
all loop sounder circuit controllers set as Device Output or Supervised Device Output
and linked to Fire Protection in the Output Menu