Zone menu
(DEVICE MENU, 2,
)
ZONE
Coincidence I.S. Zone
:dis
Zone
:1
on/off
:dis
Status
:en
Day/Night
:dis
Mode
:normal
Sounder Delay
:dis
Area
:1
Fbrig Delay
:dis
0. .9,
^V,
<>,
E,
X
Alarms: 1
Faults: 0
Cond.: 0
P: 1
SDZ
Return to Device Menu
Page 78
Select field to be changed
Enter number 0..9 or
to change data (Unlock memory!)
Confirm entry
For Zone Text Field (1 line x 40 characters):
Use
to obtain the text line to be changed
Press
(Unlock memory!)
Use
to toggle between alpha and numeric text
Press the alpha/numeric button required
Use
to move the cursor within the line
Press
when completed
The operation of each zone can be viewed and modified using this menu.
The functions of the screen are:
•
Zone:
1—112
- Select the zone to be viewed or modified.
•
Status:
enable/disable
- Zones can be enabled or disabled. When
disabled, the zone fault LED remains
steady on. In addition, the common fault
and common disable LED’s are active.
Fires and faults occurring in a disabled
zone are not reported. If fires or faults exist
at the time of disabling, the panel must be
reset to clear these conditions.
Note
that
all devices in the disabled zone
remain
electrically active
and can still be viewed
in the Device Menus.
(See Page 78)
.
Zones can also be disabled using the
DISABLE function key.
(See Page 188)
A report of disabled zones can be
obtained.
(See Page 194)