Input definition – type Time
(INPUT/OUTPUT, 1,
)
INPUT DEFINITION
State
:false
Input
:1
Trig.
:latched
Type
:Time
Mode
:active
Time
:03:25
continuous
Day
:Every Day
Event
unlogged
^V,
<>,
E,
X
Alarms: 0
Faults: 0
Cond.: 0
P: 1
SDZ
Return to Input/Output Menu
Page 109
Place cursor at TYPE
Select Type: TIME and press
(Unlock memory!)
Use number 0..9 or
to set time and press
(Unlock memory!)
to select Day and press
*See Common Facilities - All Input Types, Page 111 for description of Input, State,
Trigger, Mode, Event, and Test
Inputs may be activated at a specified time on any day of the week or every day of the
week.
The time function may be considered as a contact that closes at the specified time and
day and remains closed for one minute. The input can be made to latch or pulse by
selecting different trigger and mode. Using the set and reset functions of LOGIC with two
or more time inputs can create more complex time waveforms.
Time:
Time of day in 24hr format:
hh:mm
hh 0-23 mm 0-59
The input will switch at the selected hour (hh) and minute (mm)
-
Time 00h00 has no action
Day:
Every day
Monday
Tuesday
Wednesday
Thursday
Friday
Saturday
Sunday
Trigger:
Latched/Unlatched
If the trigger condition is latched and the mode is set to continuous, the state
will change once on the set time and day and will remain so until the panel
is reset. If the mode is set to pulse, the state will change on the set time
and day, i.e. if it was true, it will change to false and vice versa.
If the trigger condition is unlatched, the state will change for one minute on
the set day and time.