The parameters set by the user are:
•
Address:
loop/address
- Select the device to be viewed.
•
Status:
enable/disable/soak
- This determines if the device is currently
active or not. When a device is in "soak",
no alarm condition or outputs will be
triggered when the device comes into
alarm — it will only be reported as an
event.
•
Zone:
1—112
- Devices are allocated to zones.
Zones may be in the displayable range of
the FP2000 as determined by the front
panel.
•
Type:
user type
- The particular device type that the user
requires
at the selected loop/address.
This is compared to the
field type
(Screen
2) which is the
actual
device type
responding to the fire panel at that
loop/address. A mismatch between the
Type and Field type will cause one of three
fault warnings:
Type
Field Type
Fault
any type
None
Communication fault
none
any type
Device disabled
any type
different type
Wrong type
The field type recognised by the fire panel is one of the following types. These types are
further expanded by the user to define the particular type. The particular user type defines
Screen 2, and in some cases the operation, for that device.
Type
Field Type
Description
1O
[1
I/O
Single channel Output unit
1I/O
[1
I/O
Single channel input single channel output unit
2I/O
[2
2I2O
2 channel input 2 channel output unit
2I1O
[1
I/O
2 channel input 1 channel output unit
3I/O
[1
I/O
Three channel I/O unit
4I/O
[2
4I4O
4 channel input 4 channel output unit
4I
[2
4I
4 channel input unit
CUM
[1
MON
Control monitor unit
GCU1
[1
I/O
I/O section of gas unit
GCU2
[1
MCP
Gas unit manual call point
ICC
[2
ICC
Indicating circuit controller
ION
ION
Ionization smoke monitor
MCP
MCP
Manual call point
MCPM
MCP
Manual call point monitor
MCPW
MCP
Manual call point warning
MUL
[1
MUL
Multi-Sensor (Optical/Heat detector)
OPT
OPT
Optical smoke monitor
SMI
[1
MCP
Switch monitor unit with interrupt
SMU
[1
MON
Switch monitor unit
SMU+
[1
MON
Switch monitor unit plus
SIM
[2
SIM
Single Input Module
SND
[1
SND
Sounder circuit controller
TEMP
TEMP
Heat detector
ZMU
[1
MON
Zone monitor unit
ZMU
[2
ZMU
Zone monitor unit
The gas control unit occupies two consecutive addresses. The first (even) address is an
I/O unit and must be set to GCU1. The second (odd) address is a MCP and must be set
to GCU2.