Zone disable
(DISABLE MENU, 1,
)
ZONE DISABLE I.S Zone :dis
Zone
:1
on/off
:dis
Status
:en
Day/Night
:dis
Mode
:normal
Sounder Delay :dis
Area
:0
Fbrig Delay
:dis
0. . 9,
^V,
<>,
E,
X
Alarms: 0
Faults: 1
Cond.: 0
P: 1
SDZ
Return to Disable Menu
Page 188
Toggle between Zone and Status
For Zone field:
or 0..9 select zone to be disabled/enabled
Confirm entry
For Status field:
select enable/disable
Confirm entry
The selected zone is disabled/enabled from the system. A disabled zone will not report
fires or faults occurring in the zone. The disabled zone is indicated by the zone fault lamp
steady on, and the common disable illuminated. A disabled zone causes a fault condition.
Existing fire or fault conditions will not be cancelled when the zone is disabled. The fire or
fault will be cleared, and not re-occur, when the panel is reset after the disablement.
Disable does not electrically disconnect the device from the loop
. Disable should not
be used if maintenance is to be done on the loop or the devices. The loop must be
physically disconnected in this case.
The Mode, Area, On/Off and Day/Night settings are displayed on this screen for
information purposes only.
*See Zone Menu (Page 96) for further information of the Zone Menu.