Clear site data 1
(SYSTEM MENU, 3,
)
CLEAR SITE DATA
1 Devices
2 Zones
3 Areas
4 Inputs
5 Outputs
6 System
7 Loops
8 Logic Table
more
0. . 9,
<>,
E,
X
Alarms: 0
Faults: 1
Cond.: 0
P: 1
SDZ
Select number or use
and press
(Unlock memory!)
When prompted for confirmation:
For Devices select loop number or use
and press
All other selections use
for YES and press
Return to System Menu
Page 25
*See also Set Default, Page 65
All or parts of the RAM memory can be cleared of data. Certain data is also pre-set as
shown below. The data blocks that can be cleared (initialised) are:
1 Devices
– Select the loop number (for all loops)
The devices of the selected loop(s) are set to:
Status:
Disabled
Type:
None
Zone:
Ø
Day level:
3
Soak test:
Disabled
Test value:
Ø
Contamination:
Ø
Statistics:
Cleared
2 Zones
– All zones are set to:
Status:
Enabled
Mode:
Normal
Area:
0
Safe Zone:
Disabled
On/Off:
Disabled
Day/Night:
Disabled
Sounder Delay:
Disabled
Fire Brigade Delay:
Disabled
3 Areas
– All areas are set to:
Status:
Enabled
Coincidence:
Unlogged
Adjacent area 1-5:
Ø
4 Inputs
– All inputs are set to:
Type:
None