Mode:
- A coincidence condition is logged in the event buffer when two
or more fire monitoring devices of the zone
are
in alarm. A
coincidence condition can also be used as an input for I/O logic
switching. When viewing the display alarm screen, the
abbreviation "COI" is displayed next to the status of devices
contributing to the coincidence condition of the zone. Also,
when viewing this zone menu, the word "COINCIDENCE"
flashes if the zone currently has a coincidence condition.
"Mode" determines the operation –
: normal – Coincidence only
: confirmed – Alarm is raised only if fire is
present for more than 60s as well as for a
coincidence.
: two devices – When first fire detected, the
panel goes into pre-alarm. During 2
nd
fire,
alarm is raised. This applies to a
coincidence as well.
•
Area:
1—99
- The selected zone can be assigned to any
one of 99 areas. An area (being a group of
zones) can be used for I/O switching and
evacuation control.
(See Page 99)
.
•
On/Off:
disable/enable
- Zones that have on/off enabled are
switched on and off each day according to
the times set in the Set Times Menu
(see
Page 68)
. This feature is intended for
security type applications (Door and I/O
monitoring) and
not
for fire zones. Any fire
monitoring device or sounder output unit
that exists in a zone that is switched off in
this manner, will cause a zone
disablement.
•
Day/Night:
disable/enable
- Zones that are enabled for day/night
operation will switch between Day Mode
and Night Mode according to the times set
in the Set Times Menu
(see Page 68)
. The
devices in these zones operate at one
level more sensitive during Night Mode
than the level set for Day Mode.
(See
Page 75)
.
•
Text:
40 chars
- Each zone can have 40 characters of user
text assigned. This text is used in the
reporting of zone faults and conditions.
•
Sounder Delay:
enable/disable
- Enables/disables the Sounder Delay (
see
Output Delays Menu and Front Panel
Keys
) for each individual zone.
This selection must be Enabled and the
front panel Sounder Delay key ON for the
delay to be enabled.
•
Fire Brigade Delay: enable/disable
- Enables/disables the Fire Brigade Delay
(see Output Delays Menu and Front Panel
Keys)
for each individual zone.
This selection must be Enabled and the
front panel Fire Brigade Delay key ON for
the delay to be enabled.